| 2003-09-29 00:00:00 | *********** UNSAT ***************** |
| | |
| | 1)NOTE: PLEASE SEE THAT PLANS ARE NOW |
| | SHOWING A COMPLETE REWIRE OF APARTMENT |
| | FROM ORIGINAL PLANS. |
| | |
| | 2)NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | ED. 210.8A6 |
| | PLEASE SEE THAT RECEPTS IN BAR AREA ARE |
| | ALSO REQ'D TO BE SHOWN AS GFI PER LOCAL |
| | AMENDMENTS. 210.8 AND NEC 2002 |
| | |
| | 3)NOTE: PLEASE SEE SD LOCATION OUTSIDE |
| | MIDDLE BEDROOM NEEDS TO BE MOVED INTO |
| | HALL IF SERVING AS ONE SD OUTSIDE ALL |
| | THREE BEDRROMS. NFPA-72 8-1.4.2 |
| | |
| | 4)NOTE: PLEASE SHOW ALL BATH RECEPTS |
| | ALSO AS GFI/GFI PROTECTED.210.8 |
| | |
| | 5)NOTE: PLEASE CLARIFY AND SHOW CONTROL |
| | FOR LOBBY HI-HATS. PLEASE SEE 210.70 AND |
| | LS 101 5-8. PLEASE NOTE, A SINGLE MEANS |
| | BY ELEVATOR WILL NOT MEET CONTROL FOR |
| | EGRESS. |
| | |
| | 6)NOTE: PLEASE PROVIDE A PANEL SCHEDULE |
| | FOR ALL MIN CIRCUITS REQD' AND LIST THE |
| | ARC FAULT PROTECTED CIRCUITS FOR ALL |
| | BEDROOMS PER 210.12 |
| | |
| | 7)NOTE: PLEASE CLARIFY AND SEE THAT AHU |
| | IS SHOWN INSIDE TOILET??? |
| | |
| | 8)NOTE: PLEASE SEE DEVICE HEIGHTS TO |
| | MEET FHAR 24 CFR 100.205 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |