2003-07-16 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03070811
 ADD: 400 N. FLAGLER# 2206
 CONT: CASTLE FLORIDA BUILDING
 TEL: (561)662-7426
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1) FL.S.S. 481.221.1(B) EACH REGISTERED
 INTERIOR DESIGNER SHALL OBTAIN A SEAL AS
 PRESCRIBED BY THE BOARD, AND ALL DRAW-
 INGS, PLANS,SPECIFICATIONS, OR REPORTS
 PREPARED OR ISSUED BY THE REGISTERED
 INTERIOR DESIGNER AND BEING FILED FOR
 PUBLIC RECORD SHALL BEAR THE SIGNATURE
 AND THE SEAL OF THE REGISTERED INTERIOR
 DESIGNER WHO PREPARED OR APPROVED THE
 DOCUMENT AND THE DATE ON WHICH THEY WERE
 SEALED. THE SIGNATURE, DATE AND SEAL
 SHALL BE EVIDENCE OF THE AUTHORITY OF
 THAT TO WHICH THEY ARE AFFIXED.
  
 2)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 THE PLAN DOES NOT GIVE A COMPLETE LAY-
 OUT OF THE UNIT, HARD TO VISULIZE THE
 COMPLETE SUITE.
  
 3) DOORS 11& 25 INDICATE NEW DOORS,
 NO RATING IS GIVEN FOR THESE DOORS.
  
 4)R-3 EGRESS DOOR/ 32" CLEAR:
 1003.2.1. THE WIDTH OF THE MEANS OF
 EGRESS SHALL BE DETERMINED FROM THE
 OCCUPANTS SERVED IN ACCORDANCE WITH
 TABLE 1004.R-3 MINIMUM CLEAR OPENING OF
 EXIT DOOR IS 32". 1012.1.1 EGRESS DOORS
 USED IN THE EXIT ACCESS SHALL PROVIDE A
 CLEAR OPENING OF NOT LESS THAN 32" WIDE.
 1012.1.7 REQUIRED EXIT DOORS SHALL BE
 OPENABLE FROM THE INSIDE WITHOUT THE USE
 OF A KEY OR TOOL, OR SPECIAL KNOWEDGE OR
 EFFORT. MANUALLY OPERATED FLUSH BOLTS OR
 SURFACE BOLTS ARE PROHIBITED. ALL HARD-
 WARE MUST BE DIRECT ACTING REQUIRING NO
 MORE THAN ONE OPERATION. NO DIMENSION
 ON WIDTH OF NEW DOOR.
  
 5) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY.
 FLAME SPREAD/ SMOKE DEVELOPMENT.
  
 6)905.2.1 RESIDENTIAL SMOKE ALARMS:
 NFPA 72.A-8-1.2.1 IN FAMILY UNITS WITH
 MORE THAN ONE BEDROOM AREA OR WITH BED-
 ROOMS ON MORE THAN ONE FLOOR, MORE THAN
 ONE SMOKE DETECTOR IS REQUIRED.
  
 7) TYPE II BUILDING, IF ANY DOOR BUCKS
 ARE REPLACED OR IF WOOD BACKING IS IN-
 STALLED IN WALLS, FIRE RETARDANT TREATED
 WOOD IS TO BE USED.
  
 8) IN BUILDING OF TYPEI ORII CONSTRUC-
 TION FLOOR FINISH IF OF COMBUSTIBLE MATE
 RIAL, SHALL BE APPLIED DIRECTLY UPON THE
 FLOOR CONSTRUCTION. IF WOOD SLEEPERS ARE
 USED SEE CODE SECTION.803.7.1
  
 9) 803.7.2 COMBUSTIBLE INSULATING BOARDS
 MAY BE USED FOR SOUND DEADENING OR INSUL
 ATING OF FLOORS, EXCEPT THAT IN BUILD-
 INGS REQUIRED TO BE TYPE I OR II
 CONSTUCTION, SUCH INSULATING BOARDS
 SHALL NOT BE MORE THAN 1/2" THICK AND CE
 MENTED DIRECTLY TO THE FLOOR SLAB.
  
 BUILDING PLAN REVIEW