| Plan Review Notes For Permit 03070793 |
| Permit Number |
03070793 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-10-07 00:00:00 | **************** USNAT ************** | | | | | | 1)NOTE: PLEASE SEE THAT NEW ELECTRICAL | | | RISER DIAGRAM IS NOW SUBMITTED. | | | PLEASE SEE MISSING REQ'D FOOTER STEEL | | | AND COLD WATER PER 250.50. | | | | | | 2)NOTE: PLEASE CORRELATE LOADS/RISER/AND | | | PANEL SCHEDULES. NO PANEL SCHEDULE/LOADS | | | SHOWN FOR A/C SUB PANEL? | | | | | | 3)NOTE: PLANS SHOW 2 A/C SYSTEMS AND YET | | | MAIN PANEL SCHEDUL ONY SHOWS ONE FEED | | | FOR AHU AND LOAD CALCS ONLY SHOW ONE | | | ALSO. PLEASE CORRELATE? | | | | | | 4)NOTE: PLEASE SEE MIN LOAD FOR DRYER | | | TO BE 5KW 220.18 | | | | | | 5)NOTE: PLEASE SEE 210.12. THE 2002 NEC | | | WENT INTO EFFECT 7/1/2003, AT THAT TIME | | | ARC FAULT PROTECTION IS REQ'D FOR MORE | | | THAN RECEPTS AS NOTED ON PLAN. | | | | | | PLEASE SEE COPY OFFS 553.80(2)(B),WITH | | | RESPECT TO DESIGNPROFESSIONAL. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE AREA ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|