Text |
| 2003-07-25 00:00:00 | ************** UNSAT **************** | | | | | | 1)NOTE: PLEASE CORRELATE RISER DIAGRAM | | | WITH PANEL SCHEDULE. 200A PANEL SHOWS | | | POOL PANEL, NOT SHOWN ON RISER. | | | | | | 2)NOTE: PLEASE SEE OCP/BRKR AND SIZING | | | FOR DRYER. PLEASE ALSO SEE WIRE SIZE. | | | | | | PLEASE NOTE, ALL OPTIONS AND PLANS WILL | | | NEED TO BE REVISED BEFORE ROUGH TO | | | WHEATHER THEY WERE INSTALLED OR NOT. | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRCIAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | | | | | | | 3)NOTE: PLEASE SUBMIT AIC RATING FOR | | | MCB SINCE THE FUSED DISC HAS BEEN | | | DELETED FROM RISER. NOTES STILL MENTION | | | FUSES TO BE USED. |
|