2003-07-25 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRAM
 WITH PANEL SCHEDULE. 200A PANEL SHOWS
 POOL PANEL, NOT SHOWN ON RISER.
  
 2)NOTE: PLEASE SEE OCP/BRKR AND SIZING
 FOR DRYER. PLEASE ALSO SEE WIRE SIZE.
  
 PLEASE NOTE, ALL OPTIONS AND PLANS WILL
 NEED TO BE REVISED BEFORE ROUGH TO
 WHEATHER THEY WERE INSTALLED OR NOT.
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRCIAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
 3)NOTE: PLEASE SUBMIT AIC RATING FOR
 MCB SINCE THE FUSED DISC HAS BEEN
 DELETED FROM RISER. NOTES STILL MENTION
 FUSES TO BE USED.