2 |
|
| Notes |
| Date |
Text |
| 2003-10-07 00:00:00 | ************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SEE A NEW RISER DIAGRAM | | | IS NOW SUBMITTED. PLEASE SEE MISSING | | | GROUNDING ELECTRODE CONDUCTOR TO BLDG/ | | | FOOTER STEEL AND COLD WATER. 250.50 | | | | | | 2)NOTE: PLEASE SEE THAT A/C SUB PANEL | | | IS NOT ON LOAD CALCS. NO LOADS/ OCO/ | | | CONDCUTOR SIZES ARE SHOWN?? | | | | | | 3)NOTE: PLEASE SEE AS OF 7/1/2003 ARC | | | FAULT PROTECTION IS NO LONGER JUST FOR | | | RECEPTS AS NOTED ON PLANS. | | | | | | 4)NOTE: PLEASE SEE LOAD FOR DRYER TO BE | | | 5KW MIN.220.18 | | | | | | PLEASE SEE ATTACHED COPY OF FS 553.80(2) | | | (B) WITH RESPECT TO DESIGN PROFESSIONALS | | | . | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|