Plan Review Notes
Plan Review Notes For Permit 03070787
Permit Number 03070787
Review Stop E
Sequence Number 2
Notes
Date Text
2003-10-07 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE SEE A NEW RISER DIAGRAM
 IS NOW SUBMITTED. PLEASE SEE MISSING
 GROUNDING ELECTRODE CONDUCTOR TO BLDG/
 FOOTER STEEL AND COLD WATER. 250.50
  
 2)NOTE: PLEASE SEE THAT A/C SUB PANEL
 IS NOT ON LOAD CALCS. NO LOADS/ OCO/
 CONDCUTOR SIZES ARE SHOWN??
  
 3)NOTE: PLEASE SEE AS OF 7/1/2003 ARC
 FAULT PROTECTION IS NO LONGER JUST FOR
 RECEPTS AS NOTED ON PLANS.
  
 4)NOTE: PLEASE SEE LOAD FOR DRYER TO BE
 5KW MIN.220.18
  
 PLEASE SEE ATTACHED COPY OF FS 553.80(2)
 (B) WITH RESPECT TO DESIGN PROFESSIONALS
 .
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]