| Notes |
| Date |
Text |
| 2003-07-25 00:00:00 | ************** UNSAT *************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATING FOR | | | NEW MCB PANEL. PLANS NOTE USE OF FUSES | | | AND THERE IS NO LONGER A FUSED MAIN | | | DISCONNECT BEING SHOWN ON RISER DIAGRAM? | | | 110.9/215.5 | | | | | | 2)NOTE: PLEASE SEE MAIN PANEL, SHOWS | | | POOL PANEL BUT POOL PANEL IS NOT SHOWN | | | ON RISER.PLEASE CORRELATE. | | | | | | 3)NOTE: PLEASE VERIFY LOAD SHOWN FOR | | | RANGE? SHOWS 3.6KW W/ A 2P-50? | | | | | | 4)NOTE: PLEASE SEE PLANS, STILL SHOW | | | MAIN DISC NEXT TO METER? | | | | | | PLEASE SUBMIT THE ABOVE INFORMAITON FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|