2003-07-25 00:00:00************** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT AIC RATING FOR
 NEW MCB PANEL. PLANS NOTE USE OF FUSES
 AND THERE IS NO LONGER A FUSED MAIN
 DISCONNECT BEING SHOWN ON RISER DIAGRAM?
 110.9/215.5
  
 2)NOTE: PLEASE SEE MAIN PANEL, SHOWS
 POOL PANEL BUT POOL PANEL IS NOT SHOWN
 ON RISER.PLEASE CORRELATE.
  
 3)NOTE: PLEASE VERIFY LOAD SHOWN FOR
 RANGE? SHOWS 3.6KW W/ A 2P-50?
  
 4)NOTE: PLEASE SEE PLANS, STILL SHOW
 MAIN DISC NEXT TO METER?
  
 PLEASE SUBMIT THE ABOVE INFORMAITON FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  