| 2003-08-07 00:00:00 | DENIED |
| | |
| | 1)FBC 1005.4.5 (GLITCH AMENDMENTS |
| | JULY 1, 2003) REQUIRES AT LEAST ONE |
| | MEANS OF ESCAPE FROM A DWELLING WHEN |
| | SHUTTERED FOR IMPACT PROTECTION. THE |
| | MEANS OF ESCAPE SHALL BE WITHIN THE |
| | FIRST FLOOR OF THE DWELLING AND CAN NOT |
| | BE LOCATED IN A GARAGE. OCCUPANTS IN ANY |
| | PART OF THE DWELLING SHALL HAVE ACCESS |
| | TO IT WITHOUT HAVING TO PASS THROUGH A |
| | LOCKABLE DOOR NOT UNDER THEIR CONTROL. |
| | INDICATE HOW COMPLIANCE WILL BE |
| | ACHIEVED. |
| | |
| | 2) FBC 1909.3 REQUIRES THE WWM IS THE |
| | SLAB TO BE SUPPORTED ON APPROVED |
| | MATERIALS AT NO MORE THAN 3 FEET OC. |
| | PLEASE INDICATE ON PLANS. |
| | |
| | 3) SPECIFY ON THE FLOOR PLAN THAT GLASS |
| | BLOCK AT ZERO LOT LINE IS REQUIRED TO |
| | BE ONE HOUR FIRE RATED. |
| | |
| | 4) THE GLASS BLOCK AT THE MASTER BATH |
| | TUB IS IN A HAZARDOUS LOCATION AND IS |
| | REQUIRED TO HAVE A MINIMUM UNIFORM FACE |
| | THICKNESS OF 0.25" PER 2405.2. PLEASE |
| | SPECIFY ON THE PLANS. |
| | |
| | 5) THE DOOR IN THE GARAGE WALL ADJACENT |
| | TO THE CONDITIONED SPACE IS REQUIRED TO |
| | BE SOLID CORE OR INSULATED PER FBC |
| | CHAPTER 13. |
| | |
| | 6) SHEET 2 OF THE PLANS LIST THE A/C |
| | AREA AS 2590 SQFT AND THE ENERGY CALCS. |
| | HAS 2579 SQFT. PLEASE CORRECT. |
| | |
| | 7) THE WINDOWS IN THE DEN EXCEED THE 20 |
| | PERCENT OF WALL AREA ALLOWED AS OPENINGS |
| | BY FBC TABLE 600. (21 SQFT ALLOWED) |
| | |
| | 8) THE LETTER FROM THE ENGINEER FOR THE |
| | GLASS BLOCK IS REQUIRED TO BE SIGNED AND |
| | SEALED WHEN SUBMITTED FOR PUBLIC RECORD |
| | PER FAC 61G15-23.002. |
| | |
| | 9) FBC 1609.4.3 DOES NOT ALLOW THE ONE- |
| | THIRD INCREASE ON THE STEEL CALCULATIONS |
| | FOR CONNECTORS. PLEASE REVISE THE |
| | CONNECTOR SCHEDULE ON SHEET 6 TO VALUES |
| | WHICH DO NOT INCLUDE THIS INCREASE. SEE |
| | THE 2003 USP AND 2002 SIMPSON HIGH WIND |
| | RESISTANT CONSTRUCTION CATALOGS. |
| | |
| | 10) HUGHES WAS PURCHASED BY USP SOME |
| | TIME AGO. PLEASE UPDATE THE HUGHES |
| | CONNECTORS SPECIFIED ON SHEET 6 AND IN |
| | THE DETAILS ON SHEET 8, TO A CURRENT |
| | MANUFACTURER. |
| | |
| | 11) PLEASE REVISE THE BUILDING CATEGORY |
| | ON SHEET 6 TO CATEGORY II. SEE TABLE 1-1 |
| | IN ASCE 7-98. R3 IS THE OCCUPANCY |
| | CLASSIFICATION. |
| | |
| | 12) NOTE 10 ON SHEET 8 REFERENCES THE |
| | WRONG CODE. PLEASE UPDATE TO 2001 FBC. |
| | |
| | 13) PROVIDE A DETAIL FOR STRUCTURAL 2X |
| | BUCKS AS REQUIRED BY THE PRODUCT |
| | APPROVAL FOR THE ENTRY DOOR. |
| | |
| | 14)FBC 1005.4.5 (GLITCH AMENDMENTS |
| | JULY 1, 2003) REQUIRES AT LEAST ONE |
| | MEANS OF ESCAPE FROM A DWELLING WHEN |
| | SHUTTERED FOR IMPACT PROTECTION. THE |
| | MEANS OF ESCAPE SHALL BE WITHIN THE |
| | FIRST FLOOR OF THE DWELLING AND CAN NOT |
| | BE LOCATED IN A GARAGE. OCCUPANTS IN ANY |
| | PART OF THE DWELLING SHALL HAVE ACCESS |
| | TO IT WITHOUT HAVING TO PASS THROUGH A |
| | LOCKABLE DOOR NOT UNDER THEIR CONTROL. |
| | INDICATE HOW COMPLIANCE WILL BE |
| | ACHIEVED. |
| | |
| | 15) THERE ARE TWO ARCHITECT'S TITLE |
| | BLOCKS ON THE PLAN. PLEASE REMOVE THE |
| | ONE THAT DOES NOT BELONG TO THE DESIGNER |
| | OF RECORD. |
| | |
| | 16) STORM PANELS: THE SAFEGUARD COMPANY |
| | IS NO LONGER IN BUSINESS AND WEATHER- |
| | GUARD HAS NOT COMPLETED THE PROCESS OF |
| | ASSUMING THE PRODUCT APPROVAL FROM SBCCI |
| | THE BUILDING OFFICIAL HAS DETERMINED |
| | THAT WE CAN NOT ACCEPT THIS PRODUCT FOR |
| | INSTALLATION IN THE CITY OF WPB AT THIS |
| | TIME. |
| | |
| | 17) PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - GLASS BLOCK |
| | |
| | 18) THE TRUSS DRAWINGS AND LAYOUT FOR |
| | SINGLE FAMILY DWELLINGS ARE NO LONGER |
| | REQUIRED TO BE SUBMITTED FOR PLAN REVIEW |
| | THEY ARE TO BE GIVEN TO THE INSPECTOR IN |
| | THE FIELD AT THE TRUSS INSPECTION. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |