| Plan Review Notes For Permit 03070768 |
| Permit Number |
03070768 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-08-21 00:00:00 | *************BUILDING FAILED************ | | | | | | 1. SUBMIT A RECORDED NOTICE OF | | | COMMENCEMENT. | | | | | | 2. TAKE 2 SETS OF PLANS TO PBC, PAY | | | IMPACT FEES.RETURN STAMPED PLANS & | | | PAID RECEIPT BEFORE A PERMIT CAN BE | | | ISSUED. | | | | | | 3. THE KEY PLAN FOR THE STORM PANELS | | | DOES NOT MATCH THE ELEVATIONS ON THE | | | PLANS. | | | | | | 4. THE PRODUCT APPROVALS FOR THE FRONT | | | ENTRY DOORS IS FOR A DOUBLE DOOR WITH | | | SIDELIGHTS.THERE ARE NO SIDELIGHS | | | SHOWN ON THE PLANS. | | | | | | 5. PLEASE HIGHLIGHT THE CORRECT GLASS | | | BLOCK SHOWN ON PLANS TO COMPLY WITH FBC. | | | | | | | | | ANY QUESTIONS PLEASE CALL: | | | LEA SMITH, BUILDING PLANS EXAMINER | | | 805-6713 |
|