Plan Review Notes
Plan Review Notes For Permit 03070764
Permit Number 03070764
Review Stop E
Sequence Number 1
Notes
Date Text
2003-07-11 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE ADDRESS THE FOLLOWING COMMENTS
 AND RESUBMIT FOR REVIEW.
  
 1} PLEASE NOTE THAT ALL PLANS
 THAT ARE SIGNED AND SEALED BY ARCH/ OR
 ENGINEER ARE REQ`D PER 61G15-23.002 FOR
 ENGINEER AND 61G1-16.004 FOR ARCH.
 SHALL HAVE A TITLE BLOCK.ALSO THE SEAL
 AND SIGNATURE MAY NOT BE COPIES.
  
 2} PLEASE ADD SMOKE DETECTORS TO COMPLY
 WITH 8-4.1.6 NFPA-72.
  
 3} PLEASE PROVIDE A PANEL SCHEDULE.
  
 4} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 5} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE PER 212-12.
  
 6} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 7} THE GROUNDING ELECTRODE FOR A 200
 AMP SERVICE IS A #4 PER 250-66,PLEASE
 INDICATE THE RATING OF THE SERVICE
 EQUIPMENT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718