| Plan Review Notes For Permit 03070764 |
| Permit Number |
03070764 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-07-11 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE ADDRESS THE FOLLOWING COMMENTS | | | AND RESUBMIT FOR REVIEW. | | | | | | 1} PLEASE NOTE THAT ALL PLANS | | | THAT ARE SIGNED AND SEALED BY ARCH/ OR | | | ENGINEER ARE REQ`D PER 61G15-23.002 FOR | | | ENGINEER AND 61G1-16.004 FOR ARCH. | | | SHALL HAVE A TITLE BLOCK.ALSO THE SEAL | | | AND SIGNATURE MAY NOT BE COPIES. | | | | | | 2} PLEASE ADD SMOKE DETECTORS TO COMPLY | | | WITH 8-4.1.6 NFPA-72. | | | | | | 3} PLEASE PROVIDE A PANEL SCHEDULE. | | | | | | 4} PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG. | | | | | | 5} PLEASE LIST THE REQ'D ARC | | | FAULT PROTECTED CIRCUITS ON PANEL | | | SCHEDULE PER 212-12. | | | | | | 6} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 7} THE GROUNDING ELECTRODE FOR A 200 | | | AMP SERVICE IS A #4 PER 250-66,PLEASE | | | INDICATE THE RATING OF THE SERVICE | | | EQUIPMENT. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|