2003-08-28 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03070731
 ADD: 1325 N CONGRESS AVE
 CONT: INNOVATIVE CONTRACTORS
 TEL: (954)781-4167
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 2ND REVIEW
 ACTION: DENIED
  
 1) COMMENT# 3 FROM 1ST REVIEW:
 SHEET A-9 INDICATES THE USE OFA FOAM
 SOFFIT, FL BLDG CODE 803.4 FOAM PLASTIC
 SHALL NOT BE USED AS AN INTERIOR TRIM.
 YOUR RESPONCE BACK, THAT IT MEETS THE
 EXCEPTION CRITERIA.
  
 THE EXCEPTION CRITERIA THAT YOU NOTE
 MUST MEET ALL OF THE (4) EXCEPTIONS.
 THE FIRST BEING 20 LBS/CU FT. THEPRO-
 DUCT TESTING REPORT SUBMITTED INDICATES
 THE DENSITY OF 1.25 LBS/PCF.
  
 THE 2ND IS MAXIMUM THICKNESS OF 1/2"
 TRIM, MAXIMUM WIDTH OF 4".
 THE DETAIL INDICATES THE WIDTH OF 4".
  
 THE TRIM MEETS THE THIRD REQUIREMENT OF
 10% OF THEWALL OR CEILING AREA.
  
 THE FLAMESPREAD RATING OF 75 NOT TO BE
 EXCEEDED. IT APPEARS TO MEET THIS
 REQUIREMENT.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715