| Notes |
| Date |
Text |
| 2003-08-28 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 03070731 | | | ADD: 1325 N CONGRESS AVE | | | CONT: INNOVATIVE CONTRACTORS | | | TEL: (954)781-4167 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | 2ND REVIEW | | | ACTION: DENIED | | | | | | 1) COMMENT# 3 FROM 1ST REVIEW: | | | SHEET A-9 INDICATES THE USE OFA FOAM | | | SOFFIT, FL BLDG CODE 803.4 FOAM PLASTIC | | | SHALL NOT BE USED AS AN INTERIOR TRIM. | | | YOUR RESPONCE BACK, THAT IT MEETS THE | | | EXCEPTION CRITERIA. | | | | | | THE EXCEPTION CRITERIA THAT YOU NOTE | | | MUST MEET ALL OF THE (4) EXCEPTIONS. | | | THE FIRST BEING 20 LBS/CU FT. THEPRO- | | | DUCT TESTING REPORT SUBMITTED INDICATES | | | THE DENSITY OF 1.25 LBS/PCF. | | | | | | THE 2ND IS MAXIMUM THICKNESS OF 1/2" | | | TRIM, MAXIMUM WIDTH OF 4". | | | THE DETAIL INDICATES THE WIDTH OF 4". | | | | | | THE TRIM MEETS THE THIRD REQUIREMENT OF | | | 10% OF THEWALL OR CEILING AREA. | | | | | | THE FLAMESPREAD RATING OF 75 NOT TO BE | | | EXCEEDED. IT APPEARS TO MEET THIS | | | REQUIREMENT. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|