| 2003-07-22 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 11 |
| | FBC-2001 AMENDMENTS CHAPTER 1 |
| | FLORIDA STATUTES |
| | |
| | 1) SHT AD-1 ALL PLUMBING PIPES THAT ARE |
| | CUT & CAPPED SHALL BE INSPECTED PRIOR TO |
| | COVERING. |
| | 2) SHT P-1 PLUMBING NOTES #9, PER SEC |
| | 90-125(B)(5) CITY CODE WPB, CONDENSATE |
| | SHALL NOT DRAIN INTO SANITARY SYSTEM. |
| | CONDENSATE SHALL DRAIN SEPARATELY OUT OF |
| | THE BLDG INTO STORM DRAIN, CATCH BASIN, |
| | OR A DRYWELL. A RELIEF VENT IS REQUIRED |
| | AS THE CONDENSATE EXITS THE BLDG. SUBMIT |
| | A DETAIL AND A RISER DIAGRAM FOR COND. |
| | 3) SHT P-1 WATER RISER DIAGRAM, FULL |
| | OPEN VALVES SHALL BE INSTALLED ON THE |
| | TOP OF EVERY WATER DOWN-FEED PIPE PER |
| | SEC 606.1(4). |
| | 4) SHT P-1 WATER RISER DIAGRAM, SHOWS A |
| | 1/2" LINE TO WD-1. THIS IS NOT FOUND ON |
| | THE PLUMBING FIXTURE SCHEDULE. PLEASE |
| | CLAIRFY. |
| | 5) SHT P-2 PLUMBING FIXTURE SCHEDULE IN- |
| | DICATES A WATER FILTER. FILTER SHALL BE |
| | NSF APPROVED. MANUF. INFORMATION REQD. |
| | SECTION 303.4 - ALSO SHOWN ON DETAIL |
| | A10 SHT P-3. |
| | 6) ENGINEERS SHALL LEGIBLY INDICATE |
| | THEIR NAME, ADDRESS, AND ENG. NUMBER ON |
| | EACH SHEET. IF PRACTICING THROUGH A DULY |
| | AUTHORIZED ENGINEERING BUSINESS, THE |
| | NAME, ADDRESS, AND ENGINEERING BUSINESS |
| | NUMBER SHALL BE LEGIBLY INDICATED ON |
| | EACH SHEET. NO ENGINEER/BUSINESS NUMBER |
| | SHOWN ON TITLE BLOCK. 61G15-23.002(2) |
| | |