2003-08-19 00:00:00*****CORRECTIONS******
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THIS IS A 27% IMPROVEMENT AND MUST
 COMPLY WITH FBC3401.7.1.2, 2003 AMEND-
 MENTS.
  
 2.)THE SIMPSON MTS16 IS A WOOD TO WOOD
 CONNECTOR, NOT A CONCRETE TO WOOD.
  
 3.)THE REVISED CONNECTION MTSM16 DOES
 NOT SPECIFY THE CORRECT ATTACHMENT
 SCHEDULE.SEE THE SIMPSON 2003
 CATALOG FOR CORRECT ATTACHMENTS.
  
 4.)HOW WILL THE NEW FOUNDATION TIE
 INTO THE EXISTING?TIE BEAM?
  
 5.)THE DOOR INFORMATION PROVIDED IS
 FOR A DOOR W/SIDELITE.REVISE THE PLAN.
  
 6.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC.
  
 7.)ONLY ONE COPY OF THE FOLLOWING
 ITEMS WERE SUBMITTED (TWO REQUIRED):
 ENERGY CALC
 SURVEY
 ROOF PRODUCT APPROVAL (MAY SUBMIT THE
 FIRST 5 PAGES, NOT ALL 55 PAGES)