Plan Review Notes
Plan Review Notes For Permit 03070535
Permit Number 03070535
Review Stop P
Sequence Number 1
Notes
Date Text
2003-07-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT A-1 DRINKING FOUNTAIN, SUBMIT A
 DETAIL SHOWING COMPLIANCE WITH 11-4.15 &
 ALL SUBSECTIONS. SHOW SPOUT HEIGHT, (11-
 4.15.2), CLEARANCES/CLEAR FLOOR SPACE,
 (11-4.15.5) ECT. - DOOR SHALL NOT SWING
 INTO THE CLEAR FLOOR SPACE REQUIRED FOR
 ANY FIXTURE. 11-4.22.2/4.23.2.
 2) SHT A-1 HANDICAP FITTING ROOM, BENCH
 SHALL BE FIXED TO THE WALL ALONG THE
 LONGEST DIMENSION. 11-4.35.4
 3) SHT A-10 DETAILS A/A-10 & B/A-10,
 PROVIDE A CLEARANCE OF AT LEAST 29"
 ABOVE THE FINISHED FLOOR TO THE BOTTOM
 OF THE APRON. (27" SHOWN) - RIM SHALL BE
 NO HIGHER THAN 34" (A.F.F). 11-4.19.2
 4) SHT M-2 WATER RISER DIAGRAM. BACKFLOW
 SHALL BE LOCATED NO MORE THAN 4' ABOVE
 THE FLOOR FOR SERVICING AND TESTING.
 5) SHT M-2 WATER RISER DIAGRAM, FLOOR
 DRAINS ARE NOT APPROVED INDIRECT WASTE
 RECEPTORS. A FLOOR SINK OR HUB DRAIN IS
 REQUIRED FOR T/P & PAN DRAIN FROM THE
 WATER HEATER. 802.3 & 802.3.2
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692