| Plan Review Notes For Permit 03070535 |
| Permit Number |
03070535 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-07-19 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | | | | 1) SHT A-1 DRINKING FOUNTAIN, SUBMIT A | | | DETAIL SHOWING COMPLIANCE WITH 11-4.15 & | | | ALL SUBSECTIONS. SHOW SPOUT HEIGHT, (11- | | | 4.15.2), CLEARANCES/CLEAR FLOOR SPACE, | | | (11-4.15.5) ECT. - DOOR SHALL NOT SWING | | | INTO THE CLEAR FLOOR SPACE REQUIRED FOR | | | ANY FIXTURE. 11-4.22.2/4.23.2. | | | 2) SHT A-1 HANDICAP FITTING ROOM, BENCH | | | SHALL BE FIXED TO THE WALL ALONG THE | | | LONGEST DIMENSION. 11-4.35.4 | | | 3) SHT A-10 DETAILS A/A-10 & B/A-10, | | | PROVIDE A CLEARANCE OF AT LEAST 29" | | | ABOVE THE FINISHED FLOOR TO THE BOTTOM | | | OF THE APRON. (27" SHOWN) - RIM SHALL BE | | | NO HIGHER THAN 34" (A.F.F). 11-4.19.2 | | | 4) SHT M-2 WATER RISER DIAGRAM. BACKFLOW | | | SHALL BE LOCATED NO MORE THAN 4' ABOVE | | | THE FLOOR FOR SERVICING AND TESTING. | | | 5) SHT M-2 WATER RISER DIAGRAM, FLOOR | | | DRAINS ARE NOT APPROVED INDIRECT WASTE | | | RECEPTORS. A FLOOR SINK OR HUB DRAIN IS | | | REQUIRED FOR T/P & PAN DRAIN FROM THE | | | WATER HEATER. 802.3 & 802.3.2 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|