2003-07-21 00:00:00************** UNSAT *************
  
 1)NOTE: PLEASE SEE 310.16 FOR SIZING
 OF FEEDERS/CONDUCTORS TO PANEL FROM 400A
 MAIN. SHOWN AS 250MCM (RATED FOR255A)
 110.14.PLEASE ADJUST OCP OR CONDUCTORS
  
 2)NOTE: PLEASE SHOW TRACK LIGHTING LOADS
 PER 220.12B
  
 3)NOTE; PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125% 215.3/230.42 ETC.
  
 4)NOTE: PLEASE SHOW CIRCUITING OF EM/EXT
 LTS PER 700.12E
  
 5)NOTE: PLEASE CLARIFY METHOD OF EQUIP-
 -MENT GROUNDING FROM MAIN TO PANEL AND
 FROM PANEL TO RTU`S. 250.110/250.122
  
 6)NOTE: PLEASE SEE ATTACHED COPIES OF
 FAC 61G15-23.002 FOR ENGINEER AND
 61G1-16.004 FOR ARCH. PLEASE SEE MISSING
 INFORMATION REQ'D ON TITLE BLOCKS FOR
 BOTH ARCH AND ENGINEER OF RECORD. PLEASE
 SEE THAT TITLE BLOC K IS MISSING FOR
 ENGINEER.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  