| Plan Review Notes For Permit 03070535 |
| Permit Number |
03070535 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-07-21 00:00:00 | ************** UNSAT ************* | | | | | | 1)NOTE: PLEASE SEE 310.16 FOR SIZING | | | OF FEEDERS/CONDUCTORS TO PANEL FROM 400A | | | MAIN. SHOWN AS 250MCM (RATED FOR255A) | | | 110.14.PLEASE ADJUST OCP OR CONDUCTORS | | | | | | 2)NOTE: PLEASE SHOW TRACK LIGHTING LOADS | | | PER 220.12B | | | | | | 3)NOTE; PLEASE SHOW ALL CONTINUOUS LOADS | | | AT 125% 215.3/230.42 ETC. | | | | | | 4)NOTE: PLEASE SHOW CIRCUITING OF EM/EXT | | | LTS PER 700.12E | | | | | | 5)NOTE: PLEASE CLARIFY METHOD OF EQUIP- | | | -MENT GROUNDING FROM MAIN TO PANEL AND | | | FROM PANEL TO RTU`S. 250.110/250.122 | | | | | | 6)NOTE: PLEASE SEE ATTACHED COPIES OF | | | FAC 61G15-23.002 FOR ENGINEER AND | | | 61G1-16.004 FOR ARCH. PLEASE SEE MISSING | | | INFORMATION REQ'D ON TITLE BLOCKS FOR | | | BOTH ARCH AND ENGINEER OF RECORD. PLEASE | | | SEE THAT TITLE BLOC K IS MISSING FOR | | | ENGINEER. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|