2003-07-22 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03070535
 ADD:1801 PALM BCH LAKES BLVD/ 158
 CONT:PLAN REVIEW
 RECTENWALD BROTHERS
 TEL: (724)772-8282
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1) 1013.8 EDGE PROTECTION. EDGE PROTEC-
 TION OF RAMP SHALL COMPLY WITH 1013.8.1
 OR 1013.8.2. EDGE PROTECTION OF RAMP
 SHALL NOT INTERFERE WITH THE CLEAR FLOOR
 SPACE REQUIRED WITH DOOR SWING INTO THE
 HANDICAPPED RESTROOM.
  
 2)11-4.1.3(3) GROUND & FLOOR SURFACES
 ALONG ACCESSIBLE ROUTES & IN ACCESSIBLE
 ROOMS & SPACES SHALL COMPLY WITH
 11-4.5. SEE ADDAAG A4.5.1 (GUIDELINE)
 A STATIC COEFFICIENT OF FRICTION OF 0.6
 IS RECOMENDED FOR ACCESSIBLE ROUTES
 AND 0.8 FOR RAMPS.
  
 3)11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL. THE DOOR LEADING INTO THE
 HANDICAPPED CHANGING ROOM TO BE 18"
 CLEAR ON THE LATCH SIDE.
  
 4) 11-4.35 DRESSING & FITTING ROOMS.
 BENCH 11-4.35.4 A 24"X48" BENCH SHALL BE
 FIXED TO THE WALL ALONG THE LONGER DIMEN
 SION.11-4.35.2 CLEAR FLOOR SPACE FOR A
 WHEELCHAIR TO BE ABLE TO MAKE A 180
 DEGREE TURN. 11-4.35.5 MIRRORS SEE
 CODE SECTION.
  
 5)1204.2 SURROUNDING MATERIALS;
 THE WALLS & FLOORS OF ALL PUBLIC REST-
 ROOMS SHALL BE LINED WITH NONABSORBANT
 MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE
 FLOOR.
  
 6)1511.7 ROOF MOUNTED MECHANICAL UNIT
 S SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGHT IN ACCORDANCE WITH TABLE 1511.7.
 MECH. 301.13 WIND RESISTANCE.
 MECHANICAL EQUIPMENT, APPLIANCES AND SUP
 PORTS THAT ARE EXPOSED TO WIND SHALL BE
 DESIGNED AND INSTALLED TO RESIST THE
 WIND PRESSURES ON THE EQUIPMENT & THE
 SUPPORTS AS DETERMINED IN ACCORDANCE
 WITH THE FL BLD CODE. THIS MAY BE ACCOMP
 LISHED BY DESIGN OR BY APPLICATION OF
 SECTION 301.13.1.
 PROVIDE TIE DOWN INFORMATION OF THE
 ROOF TOP UNITS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026