| 2003-07-22 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 03070535 |
| | ADD:1801 PALM BCH LAKES BLVD/ 158 |
| | CONT:PLAN REVIEW |
| | RECTENWALD BROTHERS |
| | TEL: (724)772-8282 |
| | |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | ACTION: DENIED |
| | |
| | 1) 1013.8 EDGE PROTECTION. EDGE PROTEC- |
| | TION OF RAMP SHALL COMPLY WITH 1013.8.1 |
| | OR 1013.8.2. EDGE PROTECTION OF RAMP |
| | SHALL NOT INTERFERE WITH THE CLEAR FLOOR |
| | SPACE REQUIRED WITH DOOR SWING INTO THE |
| | HANDICAPPED RESTROOM. |
| | |
| | 2)11-4.1.3(3) GROUND & FLOOR SURFACES |
| | ALONG ACCESSIBLE ROUTES & IN ACCESSIBLE |
| | ROOMS & SPACES SHALL COMPLY WITH |
| | 11-4.5. SEE ADDAAG A4.5.1 (GUIDELINE) |
| | A STATIC COEFFICIENT OF FRICTION OF 0.6 |
| | IS RECOMENDED FOR ACCESSIBLE ROUTES |
| | AND 0.8 FOR RAMPS. |
| | |
| | 3)11-4.13.6 MANEUVERING CLEARENCES |
| | AT DOORS. MINIMUM MANEUVERING CLEARENCES |
| | AT DOORS THAT ARE NOT AUTOMATIC OR |
| | POWER-ASSISTED SHALL BE AS SHOWN IN |
| | FIG. 25. THE FLOOR OR GROUND AREA WITH |
| | IN THE REQUIRED CLEARENCES SHALL BE |
| | CLEAR & LEVEL. THE DOOR LEADING INTO THE |
| | HANDICAPPED CHANGING ROOM TO BE 18" |
| | CLEAR ON THE LATCH SIDE. |
| | |
| | 4) 11-4.35 DRESSING & FITTING ROOMS. |
| | BENCH 11-4.35.4 A 24"X48" BENCH SHALL BE |
| | FIXED TO THE WALL ALONG THE LONGER DIMEN |
| | SION.11-4.35.2 CLEAR FLOOR SPACE FOR A |
| | WHEELCHAIR TO BE ABLE TO MAKE A 180 |
| | DEGREE TURN. 11-4.35.5 MIRRORS SEE |
| | CODE SECTION. |
| | |
| | 5)1204.2 SURROUNDING MATERIALS; |
| | THE WALLS & FLOORS OF ALL PUBLIC REST- |
| | ROOMS SHALL BE LINED WITH NONABSORBANT |
| | MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE |
| | FLOOR. |
| | |
| | 6)1511.7 ROOF MOUNTED MECHANICAL UNIT |
| | S SHALL BE MOUNTED ON CURBS RAISED A |
| | MINIMUM OF 8 INCHES ABOVE THE ROOF SUR- |
| | FACE, OR WHERE ROOFING MATERIALS EXTEND |
| | BENEATH THE UNIT, ON RAISED EQUIPMENT |
| | SUPPORTS PROVIDING A MINIMUM CLEARENCE |
| | HEIGHT IN ACCORDANCE WITH TABLE 1511.7. |
| | MECH. 301.13 WIND RESISTANCE. |
| | MECHANICAL EQUIPMENT, APPLIANCES AND SUP |
| | PORTS THAT ARE EXPOSED TO WIND SHALL BE |
| | DESIGNED AND INSTALLED TO RESIST THE |
| | WIND PRESSURES ON THE EQUIPMENT & THE |
| | SUPPORTS AS DETERMINED IN ACCORDANCE |
| | WITH THE FL BLD CODE. THIS MAY BE ACCOMP |
| | LISHED BY DESIGN OR BY APPLICATION OF |
| | SECTION 301.13.1. |
| | PROVIDE TIE DOWN INFORMATION OF THE |
| | ROOF TOP UNITS. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |