| Plan Review Notes For Permit 03070530 |
| Permit Number |
03070530 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-08-13 00:00:00 | *********** NOTE ********* | | | | | | 1)NOTE: PLEASE SEE THAT OCP AND AWG | | | FOR GEN LTS IS STILL BEING SHOWN AT | | | 60A AND #6. | | | THIS HAS BEEN REDLINED ON ALL PREVIOUS | | | PLANS BUT NEEDS TO BE CORRECTED FOR | | | FUTURE SETS. | | | | | | 2)NOTE: PLANS ARE ALSO MISSING REQ`D SD | | | AT BOTTOM OF STAIRS. SD'S TO BE IN THE | | | IMMEDIATE VICINITY LEADING TO THE FLOOR | | | ABOVE. NFPA-72 2-5.2.1.6, 8-1.4.2 | | | SD OUTSIDE MASTER BEDROOM CAN BE MOVED | | | OVER TO MEET BOTH OUTSIDE BEDRM AND | | | SERVING FOR STAIRS. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|