Plan Review Notes
Plan Review Notes For Permit 03070530
Permit Number 03070530
Review Stop B
Sequence Number 1
Notes
Date Text
2003-08-21 00:00:00DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) SUBMIT A SOIL BORING TEST REPORT AS
 REQUIRED BY FBC 1804.2.2.
  
 4) THE GLASS BLOCK IN THE MASTER BATH
 SHOWER AND AT THE TUB IN SECOND FLOOR
 BATH 2 ARE IN HAZARDOUS LOCATIONS AND
 ARE REQUIRED TO HAVE A MINIMUM UNIFORM
 FACE THICKNESS OF 0.25" PER FBC 2405.2.
  
 5) THE FULL BATH ON THE FIRST FLOOR IS
 REQUIRED TO HAVE A DOOR WITH A 29" CLEAR
 OPENING PER FBC 11-4.23.2.
  
 6) THE GIRDER ABOVE THE FAMILY ROOM NEAR
 THE KITCHEN HAS A TAG THAT CALLS FOR 2
 9/11 ANCHORS. PLEASE CLARIFY.
  
 7) SPECIFY WHAT ANCHORS WILL BE USED FOR
 EACH END OF THE TRIPLE 2X8 INSERT HEADER
 AT THE COVERED LANAI. SPECIFY THE
 ANCHORS THAT WILL BE USED TO ATTACH THE
 TRUSSES TO THE HEADER. INDICATE HOW
 THESE TRUSSES WILL BE ATTACHED TO THE
 SECOND FLOOR WALL. PROVIDE DETAILS.
 SEE FBC 104.2.1.2
  
 8) THE OVERHEAD GARAGE DOOR PRODUCT
 APPROVAL DOES NOT MEET THE PRESSURES
 LISTED IN THE WINDLOAD SCHEDULE ON A1.
  
 9) THE SH35 WINDOWS (W) AND (Y) WILL
 REQUIRE 3/16" TEMPERED GLASS TO MEET THE
 SPECIFIED WINDLOADS ACCORDING TO THE
 PRODUCT APPROVAL THAT WAS SUBMITTED.
  
 10) THE PRODUCT APPROVAL FOR THE DOUBLE
 OUTSWING ENTRY DOOR DOES NOT MEET THE
 WINDLOAD PRESSURES LISTED ON THE PLANS.
  
 11) THE 66" X 72" F.G. WINDOW (I) DOES
 NOT MEET THE WINDLOAD PRESSURES LISTED
 ON THE PLANS.
  
 12) PLEASE REVIEW THE WINDLOAD PRESSURES
 ON THE PLANS, THEY MAY BE HIGHER THAN
 REQUIRED FOR EXPOSURE B.
  
 13) PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR THE ARCHED TOP FIXED GLASS
 (TOMBSTONE) WINDOWS (A2,A3,A4 AND F).
  
 14) THE STORM PANEL KEY PLAN AND
 SCHEEDULE ARE MISSING AN OPENING ON THE
 SECOND FLOOR. THE OPENING SIZES LISTED
 ON THE SCHEDULE DO NOT CORRESPOND WITH
 THE WINDLOAD SCHEDULE OPENING SIZES FOR
 SOME OF THE GLAZED OPENINGS. SOME OF THE
 SPECIFIED PANEL LENGTHS ARE LESS THAN
 THE MINIMUM LENGTHS PERMITTED BY THE
 PRODUCT APPROVALS. THE CALK-IN ANCHORS
 SPECIFIED ARE NOT ALLOWED FOR C1
 CONNECTION TYPES IN HOLLOW CONC. BLOCK.
 PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714