| Date |
Text |
| 2003-09-08 00:00:00 | DENIED |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) ONE SET OF ENERGY CALCULATIONS IS |
| | FOR ANOTHER MODEL. TWO SETS ARE REQUIRED |
| | PLEASE REMOVE THE INCORRECT SET AND |
| | SUBMIT TWO COMPLETE SETS. |
| | |
| | 3) THE REVISED DETAIL 1 ON SHEET 4 IS |
| | STILL INCORRECT. FBC 1707.4.4.2 REQUIRES |
| | THE BUCK TO EXTEND BEYOND THE INTERIOR |
| | FACE OF THE WINDOW OR DOOR FRAME SUCH |
| | THAT FULL SUPPORT OF THE FRAME IS |
| | PROVIDED. |
| | |
| | 4) SHEET 2 OF THE PLANS CONTAINS |
| | STRUCTURAL INFORMATION AND THE TITLE |
| | BLOCK OF THE ENGINEER. THE ENGINEER IS |
| | RESPONSIBLE FOR THE STRUCTURAL DESIGN |
| | AND IS REQUIRED TO SIGN AND SEAL THIS |
| | SHEET. SEE FAC 61G15-23.002. |
| | |
| | 5) THE NORANDEX SITE SPECIFIC PRODUCT |
| | APPROVALS ARE REQUIRED TO BE SIGNED AND |
| | SEALED BY THE DESIGNER OF RECORD. IF THE |
| | DESIGNER OF RECORD DOES NOT WISH TO SEAL |
| | THE FORM, A SIGNED AND SEALED LETTER |
| | FROM THE DESIGNER OF RECORD SPECIFYING |
| | THE PRODUCT AND SPECIFIC SITE LOCATION, |
| | STATING THAT THE PRODUCT HAS BEEN |
| | REVIEWED AND IS ACCEPTABLE FOR USE IN |
| | THE STRUCTURE. |
| | |
| | 6) THE PRODUCT APPROVALS FOR THE STORM |
| | PANELS ARE ILLEGIBLE. SUBMIT CLEAR |
| | COPIES. THE STORM PANEL DRAWINGS ARE |
| | STAMPED FOR ONE PERMIT ONLY. THEREFORE, |
| | A SIGNED AND SEALED COPY OF THE DRAWINGS |
| | IS REQUIRED FOR EACH PERMIT. |
| | |
| | 7) THE TWO "USP" TA STRAPS LISTED AS A-4 |
| | IN THE TRUSS CONNECTOR SCHEDULE WITH |
| | (5) 10D X 1-1/2" NAILS AND AN UPLIFT OF |
| | 1432# IS INCORRECT. THE UPLIFT VALUE |
| | LISTED IN THE 2003 "USP" CATALOG IS |
| | 1230#. PLEASE CORRECT. SEE ATTACHED. |
| | |
| | 8) THE SURVEY INDICATES THAT THE |
| | STRUCTURE IS LOCATED IN A "B" FLOOD |
| | ZONE. THE CITY'S RECORDS SHOW IT IN AN |
| | "AO" FLOOD ZONE. PLEASE SUBMIT CORRECTED |
| | SURVEY. |
| | |
| | 9) SUBMIT CLEAR READABLE COPIES OF THE |
| | PRODUCT APPROVALS FOR THE OUTSWING DOOR |
| | WITH SIDELITE. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL. |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |