| 2003-07-31 00:00:00 | BUILDING DENIED |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) ONE SET OF THE ENERGY CALCULATIONS IS |
| | FOR THE WRONG MODEL. |
| | |
| | 3) PLEASE REVISE DETAIL 1 ON SHEET 4. |
| | THE BUCK IS REQUIRED TO EXTEND BEYOND |
| | THE INTERIOR FACE OF THE WINDOW OR DOOR |
| | FRAME. SEE FBC 1707.4.4.2(GLITCH AMEND.) |
| | |
| | 4) SPECIFY THE SIZE OF THE COLUMN AT THE |
| | REAR PORCH. |
| | |
| | 5) SPECIFY THE CONNECTOR FOR THE WOOD |
| | BEAM AT THE REAR PORCH WHERE IT CONNECTS |
| | TO THE WALL AT THE MASTER BED ROOM. |
| | |
| | 6) THE ENGINEER IS REQUIRED TO SIGN AND |
| | SEAL THE STRUCTURAL PLAN SHEETS ON |
| | WHICH HIS TITLE BLOCK APPEARS. SEE FAC |
| | 61G15-23.002. |
| | |
| | 7) THE NORANDEX SITE SPECIFIC PRODUCT |
| | APPROVALS ARE REQUIRED TO BE SEALED BY |
| | THE DESIGNER OF RECORD. THE ENGINEER'S |
| | NAME, ADDRESS AND NUMBER ARE REQUIRED TO |
| | BE ON THE FORM. SEE FAC 61G15-23.002. |
| | |
| | 8) PLEASE REVIEW THE REQUIRED DESIGN |
| | PRESSURES FOR THE GARAGE DOOR ON SHEET |
| | 3C. THEY APPEAR TO BE INCORRECT. |
| | |
| | 9) THE PRESSURES FOR THE GARAGE DOOR ON |
| | SHEET 3A ARE BOTH NEGATIVE. PLEASE |
| | CORRECT. |
| | |
| | 10) THE PRODUCT APPROVALS FOR THE STORM |
| | PANELS ARE ILLEGIBLE AND THE CIRCLED |
| | INSTALLATION INFORMATION DOES NOT APPEAR |
| | TO CORRESPOND WITH THE STORM PANEL |
| | CONNECTION DETAILS ON SHEET TWO OF THE |
| | PLANS. ONE OF THE KEY PLANS AND SCHEDULE |
| | IS FOR ANOTHER MODEL. THE DRAWINGS HAVE |
| | BEEN STAMPED BY THE ENGINEER FOR ONE |
| | PERMIT ONLY. AN ORIGINAL SIGNED AND |
| | SEALED COPY OF THE DRAWING IS REQUIRED. |
| | |
| | 11) THE TWO USP TA STRAPS LISTED AS A-4 |
| | IN THE TRUSS CONNECTOR SCHEDULE HAVE AN |
| | UPLIFT VALUE OF 1230# ON A 1 PLY TRUSS. |
| | PLEASE REVISE. FBC 1609.4 NO LONGER |
| | ALLOWS A ONE-THIRD INCREASE IN THE |
| | STEEL CALCULATIONS OF CONNECTORS. PLEASE |
| | REVIEW THE VALUES LISTED AND REVISE IF |
| | REQUIRED. SEE FBC 1609.4 AND 2003 USC |
| | CATALOG. |
| | |
| | 12) SURVEY INCORRECTLY LISTS FLOOD ZONE |
| | AS B. CITY RECORDS SHOW THAT PROPERETY |
| | IS IN AN AO FLOOD ZONE. PLEASE CORRECT. |
| | AN ELEVATION CERTIFICATE WILL BE |
| | REQUIRED. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |