| 2003-09-08 00:00:00 | DENIED |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) THE SURVEY INDICATES THE STRUCTURE IS |
| | LOCATED IN A "B" ZONE. THE CITY'S RECORD |
| | INDICATES THAT IT IS IN AN "AO" ZONE. |
| | PLEASE CORRECT THE SURVEY. |
| | |
| | 3) SHEET 2 OF THE PLANS CONTAINS |
| | STRUCTURAL INFORMATION AND THE TITLE |
| | BLOCK OF THE ENGINEER. THE ENGINEER IS |
| | REQUIRED TO SIGN AND SEAL THIS SHEET. |
| | SEE FAC 61G15-23.002. |
| | |
| | 4) THE REVISED DETAIL 1 ON SHEET 4, IS |
| | STILL INCORRECT. FBC 1707.4.4.2 REQUIRES |
| | THE BUCK TO EXTEND BEYOND THE INTERIOR |
| | FACE OF THE WINDOW OR DOOR FRAME SUCH |
| | THAT FULL SUPPORT OF THE FRAME IS |
| | PROVIDED. |
| | |
| | 5) THE NORANDEX SITE SPECIFIC PRODUCT |
| | APPROVALS ARE REQUIRED TO BE SEALED BY |
| | THE DESIGNER OF RECORD. IF THE DESIGNER |
| | OF RECORD DOES NOT WISH TO SEAL THE FORM |
| | A SIGNED AND SEALED LETTER FROM THE |
| | DESIGNER SPECIFYING THE PRODUCT AND THE |
| | LOCATION OF THE STRUCTURE, STATING THAT |
| | THE PRODUCT HAS BEEN REVIEWED AND IS |
| | ACCEPTABLE FOR USE IN THE STRUCTURE. |
| | |
| | 6) THE PRODUCT APPROVAL FOR THE STORM |
| | PANELS ARE ILLEGIBLE. SUBMIT CLEAR |
| | COPIES. THE DRAWINGS FOR THE STORM |
| | PANELS HAVE A STAMP ON THEM THAT |
| | INDICATES THEY ARE FOR ONE PERMIT ONLY. |
| | THIS MEANS THAT A SIGNED AND SEALED |
| | COPY OF THE DRAWINGS IS REQUIRED FOR |
| | EACH PERMIT. SUBMIT A KEY PLAN AND |
| | INSTALLATION SCHEDULE FOR THE STORM |
| | PANELS. |
| | |
| | 7) THE PRODUCT APPROVAL FOR THE OUTSWING |
| | DOOR WITH A SIDELITE IS ILLEGIBLE. |
| | SUBMIT CLEAR COPIES ALONG WITH THE |
| | APPROVED DRAWINGS (# S-2188). |
| | |