Plan Review Notes
Plan Review Notes For Permit 03070398
Permit Number 03070398
Review Stop E
Sequence Number 2
Notes
Date Text
2004-02-11 00:00:00DENIED
 ~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE ORIGINAL PLANS SHOW A 225 AMP
 SERVICE ON THE GARAGE AND A 150 AMP
 EXTERIOR PANEL ON THE HOUSE.THE
 "REVISED LOW VOLTAGE PLANS" SHOW A 200
 AMP SERVICE ON THE HOUSE AND ALSO
 SUBMITTED WAS A LOAD CALC FOR A 100 AMP
 SUB PANEL,PLEASE CORRELATE.
  
 2} SUBMIT A RISER DIAGRAM SHOWING THE
 INTENDED SCOPE OF WORK INCLUDING ALL
 CONDUIT,FEEDER AND GROUND SIZES.ALSO
 SHOW COMPLIANCE WITH 230.31 & 250.32 IF
 APPLICABLE.
  
 3} SHOW ALL EQUIPMENT LOCATIONS ON
 PLANS.
  
 4} SUBMIT LOAD CALCULATIONS FOR THE
 ENTIRE ELECTRICAL SCOPE OF WORK.
  
 5} THE "COVERED PORCH" ON THE 8- 1/2" BY
 11" THAT WAS SUBMITTED WITH THE LOW
 VOLTAGE APPLICATION DOES NOT APPEAR ON
 THE ORIGINAL PLANS,ELECTRICAL OR
 BUILDING.IF THIS IS NEW A PERMIT IS
 REQUIRED, IF EXISTING AND BEING WIRED
 NOW PLEASE ADD TO THE PLAN FOR
 REVERENCE. ALSO ADJUST THE VALUE OF THE
 REVISION TO INCLUDE ALL WORK BEING DONE.
  
 6} THE SMOKE DETECTOR THAT WAS ADDED IN
 THE KITCHEN AREA MUST BE 3' AWAY FROM
 THE DOOR AND 20' AWAY FROM A COOKING
 APPLIANCE OR MUST COMPLY WITH 8-1.4.2
 NFPA-72.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026