| 2003-08-01 00:00:00 | DENIED BY BUILDING |
| | |
| | 1) 1001.1.3/ 1005.4 ZERO LOT LINE |
| | EGRESS:WHEN ACCESS TO OR FROM A RE- |
| | QUIRED EMERGENCY ESCAPE AND RESCUE OPEN- |
| | ING OF A STRUCTURE TO THE PUBLIC WAY, |
| | REQUIRES TRANSVERSING A PROPERTY |
| | (ADJOINING LOT) THAT IS NOT PART OF THE |
| | ONE WHICH THE STRUCTURE IS LOCATED, AN |
| | EGRESS EASEMENT THROUGH THE ADJOINING |
| | PROPERTY IS REQUIRED AND SHALL BE RECORD |
| | ED IN THE COUNTY RECORDS. THIS EASEMENT |
| | SHALL BE A MINIMUM OF 3' WIDE AND NOTH- |
| | ING SHALL BE PLACED WITHIN THE EASEMENT |
| | AREA WHICH WOULD BLOCK ACCESS TO THE |
| | EASEMENT AND OR IMPEDE EMERGENCY EGRESS |
| | FROM THE RESCUE OPENING TO THE PUBLIC |
| | WAY. NO LANDSCAPING, FENCES OR OTHER |
| | IMPEDIMENTS SHALL BE INSTALLED IN THIS |
| | EASEMENT. |
| | |
| | 2)THE 23 SH WINDOW IN THE GUEST BATHROOM |
| | EXCEEDS THE 20% OF WALL AREA ALLOWED AS |
| | OPENING AREA BY FBC TABLE 600. |
| | |
| | 3) FBC 1909.3 REQUIRES WWM IN THE SLAB |
| | TO BE SUPPORTED. SPECIFY ON THE PLANS. |
| | |
| | 4) THE GLASS BLOCK AT THE TUB AREA IS |
| | REQUIRED BY FBC 2405.2 TO HAVE A UNIFORM |
| | FACE THICKNESS OF 0.25". SPECIFY ON THE |
| | PLAN. |
| | |
| | 5) THE LETTER FROM THE ENGINEER FOR THE |
| | GLASS BLOCK IS REQUIRED TO BE SIGNED AND |
| | SEALED IF SUBMITTED FOR PUBLIC RECORD. |
| | SEE FAC 61G15-23.002. |
| | |
| | 6) FBC 1609.4.3 DOES NOT ALLOW THE ONE- |
| | THIRD INCREASE ON STEEL CALCULATIONS. |
| | PLEASE REVISE THE CONNECTOR SCHEDULE ON |
| | SHEET 6 TO VALUES THAT DO NOT INCLUDE |
| | THIS INCREASE. SEE 2003 USP CATALOG AND |
| | SIMPSON HIGH WIND-RESISTANT CONSTRUCTION |
| | CATALOG. |
| | |
| | 7) THE WRONG PERMIT NUMBER IS LISTED ON |
| | THE ENERGY CALCULATIONS. PLEASE NOTE |
| | THAT THE ORIENTATION OF THE STRUCTURE |
| | MUST CORRESPOND TO THE CALCULATIONS, |
| | UNLESS THEY ARE WORST CASE CALCS. |
| | |
| | 8) PROVIDE A DETAIL FOR STRUCTURAL 2X |
| | BUCKS AS REQUIRED BY THE PRODUCT |
| | APPROVAL FOR THE ENTRY DOOR. |
| | |
| | 9) PLEASE REVISE BUILDING CATEGORY ON |
| | SHEET 6 TO II. SEE TABLE 1-1 ASCE 7-98. |
| | R3 IS THE OCCUPANCY CLASSIFICATION. |
| | |
| | 10) FBC 1005.4.5 (GLITCH AMENDMENTS) |
| | REQUIRES AT LEAST ONE MEANS OF ESCAPE |
| | FROM A DWELLING WHEN SHUTTERED FOR |
| | IMPACT PROTECTION. THE MEANS OF ESCAPE |
| | SHALL BE WITHIN THE 1ST FLOOR OF THE |
| | DWELLING AND CAN NOT BE LOCATED IN A |
| | GARAGE. OCCUPANTS IN ANY PART OF THE |
| | DWELLING SHALL HAVE ACCESS TO IT WITHOUT |
| | HAVING TO PASS THROUGH A LOCKABLE DOOR |
| | NOT UNDER THEIR CONTROL. INDICATE HOW |
| | COMPLIANCE WILL BE ACHIEVED. |
| | |
| | 11) STORM PANELS: THE SAFEGUARD COMPANY |
| | IS NO LONGER IN BUSINESS AND WEATHER- |
| | GUARD HAS NOT COMPLETED THE PROCESS OF |
| | ASSUMING THE PRODUCT APPROVAL FROM SBCCI |
| | THE BUILDING OFFICIAL HAS DETERMINED |
| | THAT WE CAN NOT ACCEPT THIS PRODUCT FOR |
| | USE IN THE CITY OF WPB AT THIS TIME. |
| | |
| | 12) THE TRUSS DRAWINGS AND LAYOUT FOR |
| | SINGLE FAMILY DWELLINGS ARE NO LONGER |
| | REQUIRED TO BE SUBMITTED FOR PLAN REVIEW |
| | THEY ARE TO BE GIVEN TO THE INSPECTOR IN |
| | THE FIELD AT THE TRUSS INSPECTION. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |