| 2003-09-23 00:00:00 | DENIED |
| | |
| | 1) THE ENGINEER'S NAME, ADDRESS AND |
| | LICENSE NUMBER IS REQUIRED ON THE PLANS |
| | AND IF PRACTICING THROUGH AN AUTHORIZED |
| | BUSINESS THE BUSINESS NAME AND LICENSE |
| | NUMBER IS REQUIRED PER FAC 61G15-23.002. |
| | THE ROOF FRAMING PLAN AND ROYALL WALL |
| | DRAWINGS ARE MISSING THIS INFORMATION. |
| | |
| | 2) THE ROOF FRAMING PLAN AND ROYALL WALL |
| | DRAWINGS HAVE NOT BEEN SEALED BY THE |
| | ENGINEER. |
| | |
| | 3) THE MANUFACTURER'S SPECS. AND LISTING |
| | INFORMATION IS REQUIRED IF INSTALLING |
| | THE OPTIONAL PREFAB FIREPLACE. IF NOT |
| | BEING INSTALLED CROSS IT OFF ON THE |
| | PLANS. |
| | |
| | 4) SUBMIT STRUCTURAL DRAWINGS FOR THE |
| | CHIMNEY. INDICATE FRAMING, STRAPPING, |
| | EXTERIOR COVERING, DIMENSIONS, ETC. |
| | |
| | 5) SEMCO AND HUGHES ARE NO LONGER IN |
| | BUSINESS. UPDATE SHEETS 6 , RF-1 AND THE |
| | ROYALL WALL DRAWINGS TO CONNECTORS THAT |
| | ARE LISTED IN THE CURRENT USP, SIMPSON, |
| | ETC. CATALOGS. |
| | |
| | 6)FBC 1005.4.5 (GLITCH AMENDMENTS |
| | JULY 1, 2003) REQUIRES AT LEAST ONE |
| | MEANS OF ESCAPE FROM A DWELLING WHEN |
| | SHUTTERED FOR IMPACT PROTECTION. THE |
| | MEANS OF ESCAPE SHALL BE WITHIN THE |
| | FIRST FLOOR OF THE DWELLING AND CAN NOT |
| | BE LOCATED IN A GARAGE. OCCUPANTS IN ANY |
| | PART OF THE DWELLING SHALL HAVE ACCESS |
| | TO IT WITHOUT HAVING TO PASS THROUGH A |
| | LOCKABLE DOOR NOT UNDER THEIR CONTROL. |
| | INDICATE HOW COMPLIANCE WILL BE |
| | ACHIEVED. |
| | |
| | 7) THE STORM PANEL INFORMATION THAT WAS |
| | SUBMITTED IS NOT ACCEPTABLE. THE SBCCI |
| | REPORT FROM AMERICAN ALUMINUM IS NO |
| | LONGER LISTED. SAFEGUARD IS NO LONGER IN |
| | BUSINESS AND WEATHERGUARD HAS NOT YET |
| | HAD SAFEGUARD'S REPORT TRANSFERED TO |
| | THEM BY SBCCI. |
| | |
| | 8) THE PRODUCT APPROVAL FOR THE MULLIONS |
| | DOES NOT APPEAR TO WORK FOR THE 12 FT. X |
| | 10 FT.2 IN. FIXED GLASS WINDOW WITH |
| | ARCHED F.G. ABOVE LOCATED IN THE GRAND |
| | ROOM. INDICATE THE LOCATIONS AND SIZES |
| | OF THE MULLIONS FOR THIS WINDOW. |
| | |
| | 9) THE TRUSS LAYOUT AND DRAWINGS ARE NOT |
| | REQUIRED TO BE SUBMITTED FOR PLAN REVIEW |
| | THE SIGNED AND SEALED SET IS REQUIRED TO |
| | BE GIVEN TO THE BUILDING INSPECTOR AT |
| | THE ROOF FRAMING INSPECTION. |
| | |