Plan Review Notes
Plan Review Notes For Permit 03070369
Permit Number 03070369
Review Stop P
Sequence Number 2
Notes
Date Text
2003-08-19 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
  
 1) SHT A1.02 BOTTLED WATER COOLER SHALL
 BE ARI-1010 COMPLIANT. MANUF. SPEC. SHTS
 REQUIRED.
 2) SHT A2.01 BREAK ROOM SINK - FROM PRE-
 VIOUS REVIEW, SHOW CLEAR FLOOR SPACE FOR
 SINK.
 3) FROM PREVIOUS REVIEW, SUBMIT A WATER
 RISER DIAGRAM. NO REVISED PLUMBING SHEET
 FOUND. SHOW ALL PIPE SIZES ECT.
 4) MANUF. SPEC. SHEETS FOR PUMP DO NOT
 INDICATE A LISTING FOR THE PRODUCT. SEC
 303.4 REQUIRES LABELING BY AN APPROVED
 AGENCY.
 5) FROM PREVIOUS REVIEW, NO VENTING RE-
 VISION SUBMITTED. (PUMP SHALL VENT TO
 EXISTING VENT SYSTEM).
 6) WHEN RESUBMITTING PLANS (TWO SETS),
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]