| Plan Review Notes For Permit 03070369 |
| Permit Number |
03070369 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-08-19 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | | | | 1) SHT A1.02 BOTTLED WATER COOLER SHALL | | | BE ARI-1010 COMPLIANT. MANUF. SPEC. SHTS | | | REQUIRED. | | | 2) SHT A2.01 BREAK ROOM SINK - FROM PRE- | | | VIOUS REVIEW, SHOW CLEAR FLOOR SPACE FOR | | | SINK. | | | 3) FROM PREVIOUS REVIEW, SUBMIT A WATER | | | RISER DIAGRAM. NO REVISED PLUMBING SHEET | | | FOUND. SHOW ALL PIPE SIZES ECT. | | | 4) MANUF. SPEC. SHEETS FOR PUMP DO NOT | | | INDICATE A LISTING FOR THE PRODUCT. SEC | | | 303.4 REQUIRES LABELING BY AN APPROVED | | | AGENCY. | | | 5) FROM PREVIOUS REVIEW, NO VENTING RE- | | | VISION SUBMITTED. (PUMP SHALL VENT TO | | | EXISTING VENT SYSTEM). | | | 6) WHEN RESUBMITTING PLANS (TWO SETS), | | | PLEASE CLEARLY INDICATE THE REVISION AND | | | REMOVE AND REPLACE ANY PAGES AS NECESS- | | | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH | | | THE PLANS WHEN RESUBMITTING PLANS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|