Plan Review Notes
Plan Review Notes For Permit 03070369
Permit Number 03070369
Review Stop E
Sequence Number 2
Notes
Date Text
2003-08-19 00:00:00************* UNSAT **************
  
 1)NOTE: PLEASE SEE 424.3B FOR OCP FOR
 AHU/HEAT @ 125%. SHOWN AS 2P50`S.
  
 2)NOTE: PLEASE CORRELATE PANELS/PLANS
 AND LOAD CALCULATIONS. SHOWS 3 A/C SYST-
 -EMS ON LOAD CALCS AND 4 ON PLANS AND
 PANEL SCHEDULES.?
  
 3)NOTE: PLEASE SEE PLANS STILL NOTE
 STANDARD BLDG CODE. WE ARE UNDER FBC
 2001.
  
 4)NOTE: PLEASE SEE 110.26 AND PROVIDE
 CLEAR FLOOR SPACE MARKINGS FOR PANELS.
 ESP STORAGE AREAS.
  
 5)NOTE: PLEASE CLARIFY WHY NEW LIGHTING
 LOADS ARE NOT REVISED TO 125% FOR
 CONTINUOUS LOADS AND SHOWN @125% ON
 EXISTING?
 215.3/230.42 ETC.
  
 6)NOTE: PLEASE REMOVE ALL OLD VOIDED
 SHEETS AND INSERT NEW SHEETS INTO TWO
 NEW COMPLETE SETS FOR REVIEW AND STAMP-
 -ING.
  
 7)NOTE; PLEASE ALSO SEE THAT VALUATION
 FOR SCOPE OF WORK HAS NOT BEEN CHANGED
 AND CONTRACT FOR COMPLETE SCOPE OF WORK
 HAS NOT BEEN PROVIDED. FAC/FBC/ CITY
 ADMIN CODE,104.6.5
  
 PLEASE SEE NOTES FROM OTHER REVIEWERS
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  