| Notes |
| Date |
Text |
| 2003-07-21 00:00:00 | *************** UNSAT ************ | | | | | | 1)NOTE: PLEASE SUBMIT PANEL(S) SCHEDULES | | | TO CORRELATE WITH CIRCUITING SHOWN ON | | | PLANS. | | | | | | 2)NOTE: PLEASE PROVIDE CIRCUITING ON | | | E2.1 | | | | | | 3)NOTE: PLEASE CLARFIY SIZE OF FPL METER | | | ALONG W/ LOAD CALCULATIONS DUE TO | | | ADDITION OF NEW A/C EQUIPMENT ETC.215.5 | | | | | | 4)NOTE: PLEASE PROVIDE NEW AND EXISTING | | | EXT/ EM LTS IN BOTH SPACES/ PLEASE LABEL | | | AS E FOR EXSITING.NOTE ALREADY MENTION | | | -S CIRCUIT PER 700-12E | | | | | | 5)NOTE: PLEASE PROVIDE COPY OF CONTRACT | | | FOR ALL WORK BEING PERFORMED. VALUE ON | | | APPLICATION IS SHOWN AT $2000.00 THIS | | | VALUE SHOULD INCLUDE ALL TRADES/LABOR | | | AND ALL MATERIALS, EVEN IF OWNER | | | SUPPLIED. PER 104.6.5 ADMIM CODE FBC. | | | AND LOCAL ADMIN CODE. | | | PLEASE ADJUST | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|