| Date |
Text |
| 2003-07-17 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 424.2 SWIMMING POOLS |
| | |
| | A) PLEASE ADJUST YOUR NOTES, DETAILS, OR |
| | SUBMITTALS TO REFLECT THE FOLLOWING IN- |
| | FORMATION REQUIRED FOR PLAN REVIEW |
| | 1) FBC-2001 SEC 424.2.6.6 ENTRAPMENT |
| | PROTECTION FOR SUCTION INLETS. (DETAIL) |
| | 2) FBC-2001424.2.6.6.3 (1,2,3) ENTRAP- |
| | MENT AVOIDANCE. (DETAIL) |
| | 3) FBC-2001 424.2.7.2 PUMPS AND EQUIP- |
| | MENT SHALL BE MOUNTED ON A SUBSTANTIAL |
| | BASE IN A MANNER THAT WILL ELIMINATE |
| | STRAIN ON PIPING. SLAB SHALL BE A NOMIN- |
| | AL 4" THICK. (DETAIL) |
| | 4) FBC-2001 424.2.9 WATER SUPPLY, LOCAL |
| | ORD. #2853-95, BACKFLOW REQUIRED ON |
| | WATER SERVICE. (ADD TO NOTES) |
| | 5) FBC-2001 424.2.14.1 SWIMMING POOL |
| | WATER HEATERS SHALL BEAR THE LABEL OF A |
| | RECOGNIZED TESTING AGENCY. MANUFACTURE |
| | SHEETS REQUIRED. (SUBMITTAL) |
| | 6) FBC-2001 424.2.14.2 WATER RETENTION, |
| | PROVIDE A POSITIVE MEANS OF RETAINING |
| | WATER IN THE HEATER WHEN PUMP IS SHUT |
| | OFF. (MANUFACTURE CUT SHEETS SUBMITTAL) |
| | 7) FBC-2001 424.2.14.4 CONNECTIONS, ALL |
| | WATER HEATING EQUIPMENT SHALL BE INSTAL- |
| | LED WITH FLANGES OR UNION CONNECTIONS |
| | ADJACENT TO THE HEATER. (ADD TO NOTES) |
| | 8) FBC02001 424.2.15 GAS PIPING SHALL |
| | COMPLY WITH FBC FUEL GAS. SEPARATE PLANS |
| | AND PERMIT REQUIRED.(ADD TO NOTES) |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |