| Plan Review Notes For Permit 03070239 |
| Permit Number |
03070239 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-07-17 00:00:00 | ************* UNSAT ***************** | | | | | | 1)NOTE: : PLEASE SHOW ALL CIRCUITING ON | | | PLANS. PLEASE CORRELATE W/ SUBMITTED | | | PANEL SCHEDULE. | | | | | | 2)NOTE: PLEASE SEE REQ'D GFI PROTECTION | | | FOR KITCHENS. 210.8B | | | | | | 3)NOTE: PLEASE SEE ATTACHED SHEET FOR | | | FAC 61G15-23.002 AND REQ'D INFORMATION | | | FOR TITLE BLOCK INCLUDING AUTHORIZATION | | | #. | | | | | | 4)NOTE: PLEASE CORRELATE CIRCUITING AND | | | PANEL SCHEDULES. CIRCUIT A-1 SHOWN AS | | | KITCHEN COUNTER RECEPT AND PANEL SHOWS | | | A/C UNITS.? | | | ALOS SHOWS SAME CIRCUIT FEEDING OTHER | | | RECEPTS FOR OTHER EQUIPMENT? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|