2003-07-21 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03070239
 ADD: 1675B FORUM PLACE
 CONT: BEJAI P MANAGAR
 TEL: (561)239-1040
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
  
 1) 11.3.3 WIDTH. THE MINIMUM CLEAR WIDTH
 OF AN ACCESSIBLE ROUTE SHALL BE 36"
 EXCEPT AT DOORS. IF A PERSON IN A WHEEL-
 CHAIR MUST MAKE A TURN AROUND AROUND AN
 OBSTRUCTION, THE MINIMUM CLEAR WIDTH OF
 THE OBSTRUCTION, THE MINIMUM CLEAR WIDTH
 OF THE ACCESSIBLE ROUTE SHALL BE AS
 SHOWN IN FIGURE 7(A) AND (B).
  
 2)11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 3) 11-4.23.3 CLEAR FLOOR SPACE, AN UN-
 OBSTRUCTED TURNING SPACE COMPLYING WITH
 11-4.2.3. A HANDICAPPED PERSON CAN'T
 EVEN MAKE IT TO THE WATER CLOSET, OR
 HOLD ON TO THE GRAB BARS TO MAKE A TRANS
 FER TO THE WATER CLOSET!!!!
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026