| Plan Review Notes For Permit 03070233 |
| Permit Number |
03070233 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-07-09 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | NOTE: PLEASE NOTE THAT ALL PLANS | | | DRAWN BY AN ARCHITECT/ENGINEER CONTAIN- | | | ING A TITLE BLOCK, MUST BE SIGNED, | | | DATEDAND SEALED BY THE ARCH/ENGINEER OF | | | RECORD. PER FS/FAC 481.221 & 471.025 | | | | | | PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | PLEASE SUBMIT A RISER DIAGRAM SHOWING | | | THE GROUNDING ELECTRODE SYSTEM PER | | | 250-50 OR 250-52, WHICHEVER IS USED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|