| Notes |
| Date |
Text |
| 2003-07-08 00:00:00 | PLEASE CLARIFY HOOD #2 DUCT VELOCITY | | | INDICATES 1,059 FPM - AS PER 2001 FBC(M) | | | 506.3.6, VELOCITY SHALL BE NOT LESS THAN | | | 1,500 FPM AND NOT GREATER THAN 2,500 | | | FPM.SPOKE WITH MIKE FROM HOOD DEPOT | | | ENGINEER TO CORRECT PROBLEM & SUBMIT | | | AN AMMENDED CALCULATION FOR HOOD # 2 | | | PLANS WILL THEN BE APPROVED. |
|