| Plan Review Notes For Permit 03062223 |
| Permit Number |
03062223 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-07-01 00:00:00 | BUILDING PLAN REVIEW | | | ******PROVISO******* | | | ROBERT BROWN(561) 805 6716 | | | E-MAIL: [email protected] | | | | | | FBC = FLORIDA BUILDING CODE 2001 | | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | | | | --PROVISO-- | | | FBC 1204.2BATHROOM WALL TILE.THE | | | 'SCOPE' ON THE PLAN REFERS TO REMOVAL OF | | | WALL TILE IN BOTH BATHROOM.THE TILE | | | SHALL NOT BE REMOVED UNLESS THE WALLS | | | ARE LINED WITH NON-ABSORBENT MATERIAL | | | (E.G. NEW TILE) TO A HEIGHT OF 4 FT | | | ABOVE THE FLOOR. | | | | | | --PROVISO-- | | | FBC 11-4.13.6THE DOOR TO THE TRAINING | | | ROOM SHALL HAVE AT LEAST 18" CLEARANCE | | | BETWEEN THE LEADING EDGE OF THE DOOR AND | | | ADJACENT PERPENDICULAR WALL ON THE PULL- | | | SIDE AND 12" CLEARANCE BETWEEN THE DOOR | | | AND THE ADJACENT WALL ON THE PUSH-SIDE. |
|