| Plan Review Notes For Permit 03062200 |
| Permit Number |
03062200 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-07-15 00:00:00 | DENIED | | | | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | FBC-2001 BLDG. | | | | | | 1) SHT A1 RADIO STUDIO, SUBMIT CALCULAT- | | | IONS FOR MINIMUM FACILITIES PER TABLE | | | 1003.1 (BLDG.) AND TABLE 403.1 (PLMG.) | | | 2) SHT A2 PERTABLE 403.1 A DRINKING | | | FOUNTAIN IS REQUIRED. | | | 3) SHT A3 TOILET ROOM ELEVATIONS, HEIGHT | | | FOR W/C SHALL BE 17" TO 19" PER SECTION | | | 11-4.16.3. PLEASE INDICATE ON PLANS. | | | 4) SHT P1 PLUMBING SPECIFICATIONS #3, | | | AIR CHAMBERS ARE NOT APPROVED. PLEASE | | | DELETE FROM REFERENCE. | | | 5) SHT P2 ALL CAPPED PIPING SHALL BE IN- | | | SPECTED PRIOR TO COVERING. | | | 6) SHT P2 DOMESTIC WATER ISOMETRIC RISER | | | AIR CHAMBERS ARE NOT APPROVED. WATER | | | HAMMER ARRESTORS REQUIRED ONLY PER SEC. | | | 604.9 AT QUICK CLOSING VALVES. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 |
|