Plan Review Notes
Plan Review Notes For Permit 03062200
Permit Number 03062200
Review Stop P
Sequence Number 1
Notes
Date Text
2003-07-15 00:00:00DENIED
  
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FBC-2001 BLDG.
  
 1) SHT A1 RADIO STUDIO, SUBMIT CALCULAT-
 IONS FOR MINIMUM FACILITIES PER TABLE
 1003.1 (BLDG.) AND TABLE 403.1 (PLMG.)
 2) SHT A2 PERTABLE 403.1 A DRINKING
 FOUNTAIN IS REQUIRED.
 3) SHT A3 TOILET ROOM ELEVATIONS, HEIGHT
 FOR W/C SHALL BE 17" TO 19" PER SECTION
 11-4.16.3. PLEASE INDICATE ON PLANS.
 4) SHT P1 PLUMBING SPECIFICATIONS #3,
 AIR CHAMBERS ARE NOT APPROVED. PLEASE
 DELETE FROM REFERENCE.
 5) SHT P2 ALL CAPPED PIPING SHALL BE IN-
 SPECTED PRIOR TO COVERING.
 6) SHT P2 DOMESTIC WATER ISOMETRIC RISER
 AIR CHAMBERS ARE NOT APPROVED. WATER
 HAMMER ARRESTORS REQUIRED ONLY PER SEC.
 604.9 AT QUICK CLOSING VALVES.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692