Plan Review Notes
Plan Review Notes For Permit 03062190
Permit Number 03062190
Review Stop P
Sequence Number 1
Notes
Date Text
2003-07-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FBC-2001 AMENDMENTS, CHAPTER
 ONE, ADMIN. CODE
  
 A) SEPARATE DEMO PLUMBING PERMIT REQUIR-
 ED. ALL PIPING CAPPED OFF SHALL BE IN-
 SPECTED PRIOR TO COVERING.
 1) SHT A-2 DETAIL #3 RESTROOM ELEVATION,
 SHOW HEIGHT OF W/C SECTION 11-4.16.3 AND
 FLUSH CONTROL LOCATION 11-4.16.5
 2) SHT A-3 PLUMBING NOTES: AIR CHAMBERS
 ARE NOT APPROVED. DELETE FROM REFERENCE.
 SECTION 604.9
 3) SHT A-3 PLUMBING PLAN & RISER DIAGRAM
 ONLY THE FIXTURES WITHIN THE BATHROOM
 GROUP SHALL CONNECT TO THE WET-VENTED
 HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL
 FIXTURES SHALL DISCHARGE DOWNSTREAM OF
 THE WET VENT. DRINKING FOUNTAIN SHALL BE
 VENTED SEPARATELY. SECTION 909.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692