2003-07-09 00:00:00DENIED:PLAN CHECK
  
 1.PLAN SHEET MP-1 DETAIL OF THE THRU
 THE WALL AIR CONDITIONER, NOTE
 INDICATESCONDENSATE TO DISCHARGE TO
 NEAREST FLOORDRAIN.AS PER CITY CODE
 SEC. 90-125 (B), DISCHARGE PROHIBITIONS
 NO USER SHALL DISCHARGE INTO THE WASTE
 WATER FACILITY: (5), CONDENSATE.
  
 2.PLEASE CLARIFY FIRE RATING OF
 WALL BETWEEN THE BATTERY STORAGE AND
 OFFICE / SALES.
  