| Plan Review Notes For Permit 03061996 |
| Permit Number |
03061996 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-07-08 00:00:00 | DENIED: | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | | | | 1.MANUFACTURER SUBMITTAL DATA AND | | | INSTALLATION INSTRUCTIONS ON THE | | | MINERIAL WOOL PANEL LOCATED ABOVE THE | | | HOOD. | | | | | | 2.PLANS DO NOT INDICATE A GREASE | | | RESERVOIR OR COLLECTION. 2001 FBC(M) | | | 506.3.9. | | | | | | 3.INDICATE THE ELEVATION OF THE | | | OF THE CLEANOUT ON THE ROOF AND HOW | | | IT WILL BE ACCESSED. | | | | | | 4.TERMINATION OF THE EXHAUST SHALL | | | COMPLY WITH 2001 FBC(M) 506.3.14.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|