| Plan Review Notes For Permit 03061948 |
| Permit Number |
03061948 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-07-05 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 03061948 | | | ADD: 301 N OLIVE AVE | | | CONT: M. A. C. CONSTRUCTION | | | TEL: (786)357-0214 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | *****BUILDING PROVISO***** | | | | | | 1)704.2.1.4 CORRIDOR PARTITIONS, SMOKE | | | STOP PARTITIONS, HORIZONTAL EXIT PART- | | | ITIONS, EXIT ENCLOSURES, AND FIRE | | | RATED WALLS REQUIRED TO HAVE PROTECTED | | | OPENINGS SHALL BE EFFECTIVELY AND | | | PERMANETLY IDENTIFIED WITH SIGNS OR | | | STENCILING IN A MANNER ACCEPTABLE TO THE | | | AUTHORITY HAVING JURISDICTION. SUCH IDEN | | | TIFICATION SHALL BE ABOVE ANY DECORATIVE | | | CEILING CEILING AND IN CONCEALED SPACES. | | | SUGGESTED WORDING" FIRE & SMOKE BARRIER | | | PROTECT ALL OPENINGS". | | | | | | 2)705.7.1 JOINTS INSTALLED IN OR BE- | | | TWEEN FIRE RESISTANT WALLS, FIRE RESIS- | | | TANT FLOORS OR FLOOR/ CEILING ASSEMBLIES | | | AND FIRE RESISTANT ROOFS OR ROOF/ CEIL- | | | ING ASSEMBLIES SHALL BE PROTECTED BY AN | | | APPROVED FIRE RESISTANT JOINT SYSTEM | | | DESIGNED TO RESIST THE PASSAGE OF FIRE | | | FOR A PERIOD NOT LESS THAN THE RE- | | | QUIRED FIRE RESISTANCE RATING OF THE | | | WALL, FLOOR OR FLOOR IN OR BETWEEN | | | WHICH IT IS INSTALLED. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561)6805-6715 |
|