Plan Review Notes
Plan Review Notes For Permit 03061872
Permit Number 03061872
Review Stop P
Sequence Number 1
Notes
Date Text
2003-07-08 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FBC-2001 FUEL GAS
 FBC-2001 AMENDMENTS, CHAPTER
 ONE, ADMIN. CODE
  
 1) SHT P-0.1 PLUMBING GENERAL NOTES:
 #15 SHALL READ FBC-2001 CHAPTER 11
 #16 AIR CHAMBERS NOT APPROVED. DELETE
 FROM REFERENCE. 604.9
 PLAN NOTES #4 AIR CHAMBERS NOT APPROVED.
 DELETE FROM REFERENCE. 604.9
 2) SHT P-0.1 PLUMBING SYSTEM INSTALLAT-
 ION NOTES: TABLE 704.1 - 2-1/2" AND
 SMALLER PIPE SHALL SLOPE AT 1/4" PER FT.
 3) SHT P-0.1 GAS PIPING INSTALLATION
 NOTES: #'S 1 AND 4, NFPA-54 HAS NOT BEEN
 ADOPTED. CHANGE REFERENCE TO READ FBC-
 2001 FUEL GAS. SEC 104.2.1
 4) SHT P-0.1 PLUMBING ABBREVIATIONS AND
 PLUMBING SYMBOLS, AIR CHAMBERS ARE NOT
 APPROVED, REMOVE FROM CHARTS.104.2.1
 5) SEPARATE GAS PERMIT REQUIRED. THE
 FOLLOWING INFORMATION REQUIRED FOR GAS
 PERMIT. SECTION 104.2.1
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE. SHOW ALL PIPING BACK TO
 METER.
 B. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 D. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARD NFPA 58, AND THE FBC-2001 FUEL
 GAS CODE SEC 402.2.
 F. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. SHOW UNION
 BETWEEN MANUAL VALVE AND SOLENOID VALVE.
 **EXISTING GAS THROUGH SLAB NOT ALLOWED
 PER SECTION 404.6. PIPING SHALL NOT BE
 INSTALLED IN SOLID FLOOR SLABS, SUCH AS
 CONCRETE OR MASONRY, EXCEPT WHERE THE
 CODE OFFICIAL DETERMINES THAT THERE IS
 NO OTHER PRATICAL MANNER OF INSTALLING
 SUCH PIPING. FOR THIS TYPE OF FLOOR CON-
 STRUCTION, THE HOUSE PIPING SHALL BE IN-
 STALLED ABOVE THE FLOOR, IN AN OPEN OR
 FURRED SPACE, HOLLOW PARTITION, HOLLOW
 WALL, ATTIC SPACE OR PIPE CHASE.
 6) CONTACT RODNEY COMPO, ENVIRONMENTAL
 COMPLIANCE, INDUSTRIAL PRETREATMENT FOR
 SIZING OF THE GREASE INTERCEPTOR. WASTE
 ORD #2938-96. (561) 837-4074
 7) SHT P-1.0 WATER RISER DIAGRAM, WATER
 HAMMER ARRESTORS SHALL BE LOCATED NEAR
 THE FIXTURES IN AN "EFFECTIVE RANGE" NOT
 IN THE CEILING AS SHOWN. PDI-WH 201 AND
 MANUF. INSTALLATION INSTRUCTIONS.
 8) SHT P-1.0 DEMOLITION KEYED NOTES: #'S
 1, 2, 3, 6, & 8 NOT SHOWN ON DEMO PLAN.
 PLEASE CLAIRFY. SEC 104.2.1
 9) SHT P-1.0 KITCHEN EQUIPMENT, WATER
 FILTER SHALL BE "NSF" APPROVED. SUBMIT
 MANUF. INFORMATION.SEC 303.4
 10) SHT P-2.0 GREASE RISER DIAGRAM, ALL
 INDIRECT WASTE SHALL DRAIN INTO A FLOOR
 SINK. SECTION 802.3 - FLOOR DRAINS ARE
 NOT APPROVED INDIRECT WASTE RECEPTORS.
 11) SHT P-5.1 WATER HEATER DETAIL, SEC
 607.3.2 THERMAL EXPANSION CONTROL REQD.
 SUBMIT DETAIL.
  
 REVIEW BY KEN STEVENS