| Date |
Text |
| 2003-07-08 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 11 |
| | FBC-2001 FUEL GAS |
| | FBC-2001 AMENDMENTS, CHAPTER |
| | ONE, ADMIN. CODE |
| | |
| | 1) SHT P-0.1 PLUMBING GENERAL NOTES: |
| | #15 SHALL READ FBC-2001 CHAPTER 11 |
| | #16 AIR CHAMBERS NOT APPROVED. DELETE |
| | FROM REFERENCE. 604.9 |
| | PLAN NOTES #4 AIR CHAMBERS NOT APPROVED. |
| | DELETE FROM REFERENCE. 604.9 |
| | 2) SHT P-0.1 PLUMBING SYSTEM INSTALLAT- |
| | ION NOTES: TABLE 704.1 - 2-1/2" AND |
| | SMALLER PIPE SHALL SLOPE AT 1/4" PER FT. |
| | 3) SHT P-0.1 GAS PIPING INSTALLATION |
| | NOTES: #'S 1 AND 4, NFPA-54 HAS NOT BEEN |
| | ADOPTED. CHANGE REFERENCE TO READ FBC- |
| | 2001 FUEL GAS. SEC 104.2.1 |
| | 4) SHT P-0.1 PLUMBING ABBREVIATIONS AND |
| | PLUMBING SYMBOLS, AIR CHAMBERS ARE NOT |
| | APPROVED, REMOVE FROM CHARTS.104.2.1 |
| | 5) SEPARATE GAS PERMIT REQUIRED. THE |
| | FOLLOWING INFORMATION REQUIRED FOR GAS |
| | PERMIT. SECTION 104.2.1 |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. SHOW ALL PIPING BACK TO |
| | METER. |
| | B. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.5.2 AND TABLES 402(1) THRU |
| | 402(34). |
| | C. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). |
| | D. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARD NFPA 58, AND THE FBC-2001 FUEL |
| | GAS CODE SEC 402.2. |
| | F. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. SHOW UNION |
| | BETWEEN MANUAL VALVE AND SOLENOID VALVE. |
| | **EXISTING GAS THROUGH SLAB NOT ALLOWED |
| | PER SECTION 404.6. PIPING SHALL NOT BE |
| | INSTALLED IN SOLID FLOOR SLABS, SUCH AS |
| | CONCRETE OR MASONRY, EXCEPT WHERE THE |
| | CODE OFFICIAL DETERMINES THAT THERE IS |
| | NO OTHER PRATICAL MANNER OF INSTALLING |
| | SUCH PIPING. FOR THIS TYPE OF FLOOR CON- |
| | STRUCTION, THE HOUSE PIPING SHALL BE IN- |
| | STALLED ABOVE THE FLOOR, IN AN OPEN OR |
| | FURRED SPACE, HOLLOW PARTITION, HOLLOW |
| | WALL, ATTIC SPACE OR PIPE CHASE. |
| | 6) CONTACT RODNEY COMPO, ENVIRONMENTAL |
| | COMPLIANCE, INDUSTRIAL PRETREATMENT FOR |
| | SIZING OF THE GREASE INTERCEPTOR. WASTE |
| | ORD #2938-96. (561) 837-4074 |
| | 7) SHT P-1.0 WATER RISER DIAGRAM, WATER |
| | HAMMER ARRESTORS SHALL BE LOCATED NEAR |
| | THE FIXTURES IN AN "EFFECTIVE RANGE" NOT |
| | IN THE CEILING AS SHOWN. PDI-WH 201 AND |
| | MANUF. INSTALLATION INSTRUCTIONS. |
| | 8) SHT P-1.0 DEMOLITION KEYED NOTES: #'S |
| | 1, 2, 3, 6, & 8 NOT SHOWN ON DEMO PLAN. |
| | PLEASE CLAIRFY. SEC 104.2.1 |
| | 9) SHT P-1.0 KITCHEN EQUIPMENT, WATER |
| | FILTER SHALL BE "NSF" APPROVED. SUBMIT |
| | MANUF. INFORMATION.SEC 303.4 |
| | 10) SHT P-2.0 GREASE RISER DIAGRAM, ALL |
| | INDIRECT WASTE SHALL DRAIN INTO A FLOOR |
| | SINK. SECTION 802.3 - FLOOR DRAINS ARE |
| | NOT APPROVED INDIRECT WASTE RECEPTORS. |
| | 11) SHT P-5.1 WATER HEATER DETAIL, SEC |
| | 607.3.2 THERMAL EXPANSION CONTROL REQD. |
| | SUBMIT DETAIL. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |