| Plan Review Notes For Permit 03061872 |
| Permit Number |
03061872 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-07-09 00:00:00 | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | | | | 1.PLAN SHEET M-1.0 INDICATES A FIRE | | | DAMPER ON THE MAKE-UP AIR (SUPPLY) TO | | | THE HOOD.PLEASE CLARIFY WHY THIS IS | | | NECESSARY. | | | | | | 2.PROVIDE INFORMATION ON CLEARANCE | | | TO COMBUSTIBLES.GREASE DUCT SYSTEMS | | | SHALL HAVE A CLEARABCE TO COMBUSTIBLE | | | CONSTRUCTION OF NOT LESS THAN 18 INCHES. | | | | | | 4.ADDITIONAL PERMIT AND PLANS REQUIRED | | | FOR FIRE SUPPRESSION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|