| 2003-07-11 00:00:00 | *****CORRECTIONS****** |
| | |
| | 1.)SEE PREVIOUS CORRECTION LIST, ITEM |
| | #1.THERE IS A HOLD ON THIS PROPERTY. |
| | THE HOLD MUST BE ADDRESSED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2.)SEE PREVIOUS CORRECTION LIST, ITEM |
| | #2.THERE WAS A REQUEST TO ADD |
| | "EXTERIOR DOOR" TO THE PERMIT |
| | APPLICATION.ALSO, DIFFERENT PRODUCT |
| | APPROVALS WERE SUBMITTED WITH THIS |
| | RESUB.THE DOUBLE DOOR PA IS EXPIRED. |
| | |
| | 3.)PRODUCT APPROVALS WERE SUBMITTED |
| | FOR A GLAZED DOOR.GLAZING REQUIRES |
| | IMPACT PROTECTION FBC1606.1.4.PROVIDE |
| | TWO COPIES OF PRODUCT APPROVALS FOR |
| | THE GLAZING. |
| | |
| | 4.)PRODUCT APPROVALS WERE SUBMITTED |
| | FOR SINGLE HUNG WINDOWS.ADD WINDOWS |
| | AND SHUTTERS TO THE PERMIT APPLICATION. |
| | |
| | 5.)THE PRODUCT APPROVALS FOR THE |
| | WINDOW ARE NOT LEGIBLE.PROVIDE LEGIBLE |
| | COPIES.YOU MAY BE ABLE TO OBTAIN THEM |
| | ONLINE AT WWW.MIAMIDADE.GOV (FIND A |
| | DEPARTMENT, BUILDING CODE COMPLIANCE, |
| | PRODUCT CONTROL). |
| | |
| | 6.)PROVIDE A FOOTPRINT OF THE HOUSE. |
| | SHOW LOCATIONS, SIZE AND TYPE OF ALL |
| | WINDOWS AND DOORS TO BE REPLACED.SHOW |
| | ALL BEDROOMS AND BATHROOMS.SHOW |
| | COMPLIANCE WITH FBC1005.4 (EMERGENCY |
| | EGRESS) AND FBC 2405.1 (SAFETY GLASS). |
| | |
| | 7.)IMPACT PROTECTION REQUIRED FOR |
| | WINDOWS FBC1606.1.4. |
| | |
| | SAMANTHA THYNG, BUILDING PLANS EXAMINER |