Plan Review Notes
Plan Review Notes For Permit 03061844
Permit Number 03061844
Review Stop B
Sequence Number 1
Notes
Date Text
2003-07-11 00:00:00******CORRECTIONS*******
  
 1.)THE PROPOSED BUILDING IS LESS THAN
 3' FROM THE EXISTING HOUSE.FBC TABLE
 600 REQUIRES A 1 HR FIRE RATING FOR THE
 WALL, TO BE RATED FROM BOTH THE INSIDE
 AND THE OUTSIDE.PROVIDE CALCULATIONS
 SHOWING COMPLIANCE.
  
 2.)THE DOCUMENT PROVIDED FOR THE
 HURRICANE STORM PANELS IS NOT A PRODUCT
 APPROVAL.PROVIDE TWO COPIES OF PRODUCT
 APPROVALS.YOU MAY FIND IT ONLINE AT
 WWW.MIAMIDADE.GOV (FIND A DEPT, BUILDING
 CODE COMPLIANCE, PRODUCT CONTROL).
  
 3.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]