Plan Review Notes
Plan Review Notes For Permit 03061838
Permit Number 03061838
Review Stop E
Sequence Number 8
Notes
Date Text
2005-03-21 00:00:00********* UNSAT *******************
  
 1)NOTE: PLEASE SEE PLANS ARE REQUIRED TO
 BE SIGNED WITH LEGAL SIGNATURE FOR THE
 ENGINEER OF RECORD. PLANS DO NOT
 CORRELATE WITH PLANS ON RECORD.
 PLEASE SEE THIS IS THE SECOND TIME THIS
 HAS HAPPENED. A PREVIOUS REVIEW ON
 11/2/04 HAD THE SAME COMMENTS.
 PLEASE SEE A SET WAS RETAINED FOR FILE
 AT THAT TIME FOR POSSIBLE REVIEW BY
 FBPE'S. PLEASE SEE ONE SET OF THIS
 SUBMITTAL IS ALSO NOW RETAINED AND WILL
 BE SENT TO FBPE'S FOR REVIEW.
 PLANS MUST BE SIGNED, DATED AND SEALED
 BY THE ENGINEER OF RECORD. MULTIPLE
 SIGNATURES ARE NOT ACCEPTABLE.
 PLEASE PROVIDE IDENTIFICATON TO VERIFY.
  
 FS471.025
 FAC 61G15-23.002
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]