Plan Review Notes
Plan Review Notes For Permit 03061838
Permit Number 03061838
Review Stop P
Sequence Number 3
Notes
Date Text
2003-11-21 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SHTS P-1 & P-6 SHOW SAMPLE POINT AS
 GREASE SAMPLE POINT AND LOCATION SHALL
 BE THE SAME ON FLOOR PLAN AS RISER DIA-G
 RAM.
 2) SHT A-401 THE CALCULATIONS ON THE
 REVISED ROOF DRAINAGE CHART ARE NOT
 CORRECT. THE AREAS OF ROOFS THAT DRAIN
 ONTO ROOF AREAS ARE NOT CORRECT. THE
 AREAS OF THE VERTICAL WALLS OF WHICH 1/2
 THE AREA TO BE ADDED TO ROOF S.F. ARE
 INCORRECT. RECHECK ALL AREAS AND RESUB-
 MIT.THIS WAS COMMENT #4 FROM PREVIOUS
 REVIEW.
 3) COMMENTS #6, AND #7 FROM PREVIOUS RE-
 VIEW WILL BE ADDRESSED WHEN ROOF CALCU-
 LATIONS ARE CORRECT.
 4) SHT P-6 WATER HAMMER ARRESTORS SHALL
 ALL BE LOCATED NEAR THE FIXTURES NOT IN
 CEILING. PDI-WH 201 AND MANUF. INSTALL.
 INSTRUCTIONS.
 5) THERMAL EXPANSION CONTROL, REQUIRED
 BY SECTION 607.3.2 NOT FOUND ON SHEET
 P-1 AS INDICATED BY RESPONSE TO COMMENT
 #11 FROM PREVIOUS REVIEW.
 6) SEE COMMENT # 2 FROM ELECTRICAL RE-
 VIEW, AND SEE FS 533.80(2)(B) WITH RE-
 SPECT TO DESIGN PROFESSIONALS.
  
 REVIEW BY KEN STEVENS