| Plan Review Notes For Permit 03061838 |
| Permit Number |
03061838 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2003-11-21 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | | | | 1) SHTS P-1 & P-6 SHOW SAMPLE POINT AS | | | GREASE SAMPLE POINT AND LOCATION SHALL | | | BE THE SAME ON FLOOR PLAN AS RISER DIA-G | | | RAM. | | | 2) SHT A-401 THE CALCULATIONS ON THE | | | REVISED ROOF DRAINAGE CHART ARE NOT | | | CORRECT. THE AREAS OF ROOFS THAT DRAIN | | | ONTO ROOF AREAS ARE NOT CORRECT. THE | | | AREAS OF THE VERTICAL WALLS OF WHICH 1/2 | | | THE AREA TO BE ADDED TO ROOF S.F. ARE | | | INCORRECT. RECHECK ALL AREAS AND RESUB- | | | MIT.THIS WAS COMMENT #4 FROM PREVIOUS | | | REVIEW. | | | 3) COMMENTS #6, AND #7 FROM PREVIOUS RE- | | | VIEW WILL BE ADDRESSED WHEN ROOF CALCU- | | | LATIONS ARE CORRECT. | | | 4) SHT P-6 WATER HAMMER ARRESTORS SHALL | | | ALL BE LOCATED NEAR THE FIXTURES NOT IN | | | CEILING. PDI-WH 201 AND MANUF. INSTALL. | | | INSTRUCTIONS. | | | 5) THERMAL EXPANSION CONTROL, REQUIRED | | | BY SECTION 607.3.2 NOT FOUND ON SHEET | | | P-1 AS INDICATED BY RESPONSE TO COMMENT | | | #11 FROM PREVIOUS REVIEW. | | | 6) SEE COMMENT # 2 FROM ELECTRICAL RE- | | | VIEW, AND SEE FS 533.80(2)(B) WITH RE- | | | SPECT TO DESIGN PROFESSIONALS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|