Plan Review Notes
Plan Review Notes For Permit 03061838
Permit Number 03061838
Review Stop P
Sequence Number 2
Notes
Date Text
2003-10-07 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) PER WAIVER FOR GREASE INTECEPTOR FROM
 RODNEY COMPO A SAMPLE POINT IS REQUIRED
 ON THE GREASE SYSTEM. SHOW SAMPLE POINT
 ON GREASE RISER DIAGRAM AND ON FLOOR
 PLAN. SAMPLE POINT SHALL BE LOCATED
 DOWNSTREAM OF THE LAST FIXTURE.
 2) PLANS SHALL BE ROUTED TO THE PALM
 BEACH HEALTH UNIT. RESPONSE NOTED, BUT
 PLANS STILL NOT STAMPED. THIS WILL BE
 REQUIRED PRIOR TO PERMIT BEING ISSUED.
 3) SHEET A-401 SHOW SQUARE FOOTAGE THAT
 WILL BE DRAINED FOR EACH ROOF DOWNSPOUT
 IN AREAS RA-1 AND RA-2. IT APPEARS THAT
 THE DRAINS ARE NOT SPACED EQUALLY ALONG
 THE PARAPET WALL.
 4) SHT A-401 SHOW AREA OF ROOF FROM AREA
 RA-1 AND RA-2 THAT DRAINS ONTO THE AREAS
 OF RA-3, RA-6 & RA-7. THESE AREAS DO NOT
 SEEM TO BE CALCULATED IN LOWER ROOF
 DRAIN/SCUPPER SIZING.
 5) SHT A-401 RA-4 SCUPPERS SHALL COMPLY
 WITH 1503.4.2 FOR DISTANCE OFF ROOF TO
 THE FLOW LINE.
 6) SHT A-401 ALL ROOF AREAS, ROOF DRAINS
 ARE NOT EQUALLY SPACED. SHOW SQUARE FEET
 FOR EACH DRAIN.
 7) SHT A-403 SCUPPERS SHALL BE SIZED PER
 SECTION 1107.3
 8) SHTS P-5, P-6, & P-7 AIR CHAMBERS ARE
 NOT APPROVED. DELETE REFERENCES.
 9) PROVIDE MANUF. SPECIFICATION SHEETS
 REQUIRED FOR DUPLEX STORM WATER PUMP.
 PUMP SHALL BE LISTED. 303.4
 10) SHTP-5 STORM RISER DIAGRAM. TWO
 AREAS NOT SIZED PROPERLY. SEE 8" @
 10,508 S.F. - 10 REQD PER TABLE 1106.3.
 4" @ 2043 S.F. 5" REQUIRED ON HORIZONTAL
 6" @ 3331 S.F. REQD, NO SIZE SHOWN.
 11) SHT P-7 THERMAL EXPANSION CONTROL
 NOT SHOWN. SECTION 607.3.2
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]