| Date |
Text |
| 2003-10-07 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | |
| | 1) PER WAIVER FOR GREASE INTECEPTOR FROM |
| | RODNEY COMPO A SAMPLE POINT IS REQUIRED |
| | ON THE GREASE SYSTEM. SHOW SAMPLE POINT |
| | ON GREASE RISER DIAGRAM AND ON FLOOR |
| | PLAN. SAMPLE POINT SHALL BE LOCATED |
| | DOWNSTREAM OF THE LAST FIXTURE. |
| | 2) PLANS SHALL BE ROUTED TO THE PALM |
| | BEACH HEALTH UNIT. RESPONSE NOTED, BUT |
| | PLANS STILL NOT STAMPED. THIS WILL BE |
| | REQUIRED PRIOR TO PERMIT BEING ISSUED. |
| | 3) SHEET A-401 SHOW SQUARE FOOTAGE THAT |
| | WILL BE DRAINED FOR EACH ROOF DOWNSPOUT |
| | IN AREAS RA-1 AND RA-2. IT APPEARS THAT |
| | THE DRAINS ARE NOT SPACED EQUALLY ALONG |
| | THE PARAPET WALL. |
| | 4) SHT A-401 SHOW AREA OF ROOF FROM AREA |
| | RA-1 AND RA-2 THAT DRAINS ONTO THE AREAS |
| | OF RA-3, RA-6 & RA-7. THESE AREAS DO NOT |
| | SEEM TO BE CALCULATED IN LOWER ROOF |
| | DRAIN/SCUPPER SIZING. |
| | 5) SHT A-401 RA-4 SCUPPERS SHALL COMPLY |
| | WITH 1503.4.2 FOR DISTANCE OFF ROOF TO |
| | THE FLOW LINE. |
| | 6) SHT A-401 ALL ROOF AREAS, ROOF DRAINS |
| | ARE NOT EQUALLY SPACED. SHOW SQUARE FEET |
| | FOR EACH DRAIN. |
| | 7) SHT A-403 SCUPPERS SHALL BE SIZED PER |
| | SECTION 1107.3 |
| | 8) SHTS P-5, P-6, & P-7 AIR CHAMBERS ARE |
| | NOT APPROVED. DELETE REFERENCES. |
| | 9) PROVIDE MANUF. SPECIFICATION SHEETS |
| | REQUIRED FOR DUPLEX STORM WATER PUMP. |
| | PUMP SHALL BE LISTED. 303.4 |
| | 10) SHTP-5 STORM RISER DIAGRAM. TWO |
| | AREAS NOT SIZED PROPERLY. SEE 8" @ |
| | 10,508 S.F. - 10 REQD PER TABLE 1106.3. |
| | 4" @ 2043 S.F. 5" REQUIRED ON HORIZONTAL |
| | 6" @ 3331 S.F. REQD, NO SIZE SHOWN. |
| | 11) SHT P-7 THERMAL EXPANSION CONTROL |
| | NOT SHOWN. SECTION 607.3.2 |
| | |
| | REVIEW BY KEN STEVENS |