| Plan Review Notes For Permit 03061838 |
| Permit Number |
03061838 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2003-09-29 00:00:00 | DENIED: | | | 1.EXHAUST FANS LOCATED IN THE GARAGE - | | | PROVIDE ELEVATION FOR TERMINATION. | | | PLEASE NOTE, EXHAUST SHALL BE LOCATED | | | A MINIMUM OF 10 FT FROM LOT LINES OR | | | BUILDINGS ON THE SAME LOT AND SHALL NOT | | | BE DIRECTED ONTO WALK-WAYS. (2001 FBC(M) | | | 401.5 & 401.5.2). | | | | | | 2.PLEASE PROVIDE MANUFACTURER | | | SUBMITTAL DATA FOR THE CARBON MONOXIDE | | | SENSORS. APPROVED CARBON MONOXIDE | | | SENSORS SHALL OPERATE AUTOMATICALLY UPON | | | DETECTION OF A CONCENTRATION OF CARBON | | | MONOXIDE OF 25 PARTS PER MILLION. | | | | | | 3.FAN SHUT DOWN DUCT SMOKE DETECTORS | | | SHALL HAVE NOTIFICATION TO ALARM/STROBE | | | AS PER NFPA 90A 4-4.4.3. | | | | | | 4.CONDENSING UNIT STANDS SHALL COMPLY | | | WITH 2001 FBC 1511.7 FOR HEIGHT | | | REQUIREMENT. | | | | | | 5.ADDITIONAL PERMITS REQUIRED FOR | | | HOOD, FIRE SUPPRESSION AND WALKIN | | | COOLERS/FREEZERS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|