Plan Review Notes
Plan Review Notes For Permit 03061838
Permit Number 03061838
Review Stop M
Sequence Number 2
Notes
Date Text
2003-09-29 00:00:00DENIED:
 1.EXHAUST FANS LOCATED IN THE GARAGE -
 PROVIDE ELEVATION FOR TERMINATION.
 PLEASE NOTE, EXHAUST SHALL BE LOCATED
 A MINIMUM OF 10 FT FROM LOT LINES OR
 BUILDINGS ON THE SAME LOT AND SHALL NOT
 BE DIRECTED ONTO WALK-WAYS. (2001 FBC(M)
 401.5 & 401.5.2).
  
 2.PLEASE PROVIDE MANUFACTURER
 SUBMITTAL DATA FOR THE CARBON MONOXIDE
 SENSORS. APPROVED CARBON MONOXIDE
 SENSORS SHALL OPERATE AUTOMATICALLY UPON
 DETECTION OF A CONCENTRATION OF CARBON
 MONOXIDE OF 25 PARTS PER MILLION.
  
 3.FAN SHUT DOWN DUCT SMOKE DETECTORS
 SHALL HAVE NOTIFICATION TO ALARM/STROBE
 AS PER NFPA 90A 4-4.4.3.
  
 4.CONDENSING UNIT STANDS SHALL COMPLY
 WITH 2001 FBC 1511.7 FOR HEIGHT
 REQUIREMENT.
  
 5.ADDITIONAL PERMITS REQUIRED FOR
 HOOD, FIRE SUPPRESSION AND WALKIN
 COOLERS/FREEZERS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.