Text |
| 2003-09-17 00:00:00 | 1) COULD NOT LOCATE ANY FIRE |
| | EXTINGUISHERS WITHIN THE PARKING GARAGE |
| | AREA. |
| | |
| | 2) OVERALL SITE PLAN SA-101 DISPLAYS |
| | THE NEW FIRE HYDRANT PLANNED FOR THIRD |
| | STREET. IT APPEARS THAT A LARGE PLANT |
| | IS DIRECTLY NEXT TO THE FIRE HYDRANT. |
| | PLEASE ENSURE THAT 7'-6" IS PROVIDED |
| | TO THE FRONT AND SIDES 4' TO THE |
| | REAR. |
| | |
| | 3) WOODEN MEMBERS NOTED ON TRELLIS. |
| | PLEASE SEE APPENDIX F, LOCAL AMENDMENTS |
| | TO THE FLORIDA BUILDING CODE, FIRE |
| | LIMITS. |
| | |
| | 4) CARBON MONOXIDE DETECTORS NOTED |
| | WITHIN GARAGE. PLEASE PROVIDE |
| | PRODUCT APPROVALS. |
| | |
| | 5) WHEN A BUILDING ADDRESS IS |
| | ASSIGNED IT SHALL BE PLACED ON THE |
| | PROPER ELEVATION AND THE NUMERALS |
| | SHALL BE AT LEAST 6" HIGH. |
| | |
| | 6) YOUR PLAN REVIEW COMMENT # 23 IS |
| | NOT CORRECT. ALL SHAFTWAYS SHALL BE |
| | LABELED WITH 6" LETTERS "SHAFTWAY". |
| | PLEASE SEE NFPA 1, SECTION 3, NOT |
| | CHAPTER 6-3. |
| | |
| | 7) EXIT SIGN IS MISSING FROM NORTH |
| | SIDE OF GARAGE NEAR EXIT STAIRS ON |
| | PAGE E-04. |
| | |
| | 8) PLEASE EXPLAIN NOTE ON E-09 " UPON |
| | FLOW CONDITION ON FIRST FLOOR, THE |
| | FACP SHALL OVERRIDE THE MECHANICAL |
| | CONTROLS FOR EXHAUST FANS (EF-1, EF-2) |
| | AND SHALL INITIATE OPERATION OF THESE |
| | FANS. |
| | |
| | 9) PLEASE INDICATE WHY NO VOICE |
| | EVACUATION SPEAKER STROBES ARE BEING |
| | USED INSTEAD HORN STROBES ARE PLANNED. |
| | |
| | 10) WHY IS THE FIRE ALARM PANEL LOCATED |
| | ON THE SECOND FLOOR LEVEL. IF THE PANEL |
| | IS PLANNED FOR THE SECOND FLOOR, THEN |
| | A REMOTE ANNUNCIATOR WILL BE REQUIRED |
| | FOR THE FIRST FLOOR. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 835-2910 |