Plan Review Notes
Plan Review Notes For Permit 03061838
Permit Number 03061838
Review Stop E
Sequence Number 2
Notes
Date Text
2003-09-22 00:00:00***************** UNSAT **************
  
 PLEASE SEE THAT NOT ALL NOTES FROM
 FIRST REVIEW WERE ADDRESSED.
  
 1)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 FOR ITEMS ON ELECTRICAL PLANS THAT WILL
 HAVE AN AFFECT ON E-SHEETS.
  
 2)NOTE; PLEASE SEE FAC 61G15-23.002 FOR
 ALL INFORMATION REQ'D ON TITLE BLOCKS.
 PLEASE INCLUDE ANY CERTIFICATE OF
 AUTHORIZATION #. PLEASE SEE REG # AT
 SEAL LOCATION, SHOWN AS ALL 0'S??
 PE #'S ARE NOTED AND LOCATED.
 PLEASE PROVIDE ABOVE.
 PER FS
  
 3)NOTE: PLEASE SEE 424.3B FOR SIZING
 OF OVER CURRENT PROTECTION FOR AHU'S/
 HEAT/RTU'S. ETCMIN 125%.
  
 PLEASE NOTE, A "KNOX BOX" WILL BE REQ'D
 FOR FIRE DEPT ACCESS TO SECOND FLR AND
 ELECTRICAL ROOM. SIGNAGE WILL ALSO BE
 REQ'D. 230.2
  
 PLEASE SEE COPY OF FS 553.80(2)(B) WITH
 RESPECT TO DESIGN PROFESSIONALS.
 THIS NOTIFICATION MUST BE GIVEN FOR
 PLAN REVIEWS AFTER 2ND TIME FOR SAME
 COMMENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
 PLEASE CORRELATE PERMIT APPLICATION
 WITH PCN # SUBMITTED. COMPUTER SHOWS
 410 N OLIVE, PERMIT APPLICATION HAS 310
 N OLIVE.