| 2003-09-29 00:00:00 | |
| | BUILDING PLAN REVIEW |
| | PERMIT:03061838 |
| | ADD: 410 N OLIVE AVE |
| | CONT: G. T. MC DONALD |
| | TEL: (954)650-0022 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 2ND REVIEW: REVIEW |
| | |
| | 1) THRESHOLD BUILDING A THRESHOLD INSPEC |
| | TOR TO REGISTER WITH DON NEELY MANAGER |
| | OF OUTSIDE INSPECTOR 805-6665 |
| | |
| | 2) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 3)BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 4) A VIBROFLOTATION PERMIT (03080423) IS |
| | ISSUED, WILL THE SHEET PILING PERMIT BE |
| | PART OF THE BUILDING PERMIT OR SEPERATE |
| | PERMIT? RETAINAGE OF SOILS? |
| | |
| | 5) FL BLDG CODE 104.2.1.2 : |
| | ADDITIONAL INFORMATION REQUIRED. |
| | PLEASE PROVIDE MANUFACTURERS SPEC FOR |
| | INTERKAL TELESCOPIC SEATING. INTERKAL |
| | MAKES MORE THAN ONE LINE OF RETRACTABLE |
| | BLEACHERS, STEEL, WOOD OR PLASTIC COATED |
| | STEEL? THIS WILL EFFECT THE OUTCOME OF |
| | STEEL BAR JOIST NEEDING 1 HR PROTECTION. |
| | |
| | 6) FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORT, SBCCI OR DADE COUNTY |
| | REPORT ARE ACCEPTED. |
| | IT IS UNDERSTOOD THAT ALL OPENINGS |
| | AND OPENING PROTECTIVES ( WINDOWS, DOORS |
| | AND STORM SHUTTERS) WILL BE SUBMITTED |
| | LATER AND REQUIRE A SEPERATE PERMIT, |
| | REVIEW W/ ASSOCIATED FEES. |
| | |
| | 7) A-403 DETAIL# 5, THE FASTENING OF THE |
| | FIRE RETARDANT TREATED PLYWOOD TO THE |
| | METAL DECK? |
| | |
| | 8) GYMNASIUM BAR JOIST, TABLE 600 SHALL |
| | REQUIRE 1 HR FIREPROOFING UNLESS THE |
| | MANUFACTURERS SPEC ON THE BLECHERS INDIC |
| | ATES THERE IS NO ADDITIONAL FIRE LOAD |
| | (STEEL). THIS ISSUE WAS TAKEN TO THE |
| | B.O. UNLESS STEEL THE ENTIRE GYMASIUM |
| | STRUCTURAL SYSTEM WILL NEED TO BE HAVE |
| | FIRE PROTECTION. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |