| Date |
Text |
| 2003-07-07 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 11 |
| | FBC-2001 AMENDMENTS, CHAPTER |
| | 1, ADMIN. CODE |
| | |
| | 1) SHTS L-2.1 & L-2.2 SEPARATE IRRIGAT- |
| | ION PERMIT REQUIRED. RPZ BACKFLOW REQUI- |
| | RED IF POTABLE WATER USED FOR IRRIGATION |
| | SECTION 608.13.2 |
| | 2) GREASE INTECEPTOR SHALL BE SIZED BY |
| | RODNEY COMPO, ENVIRONMENTAL COMPLIANCE, |
| | INDUSTRIAL PRE-TREATMENT. PLEASE CONTACT |
| | @ (561) 837-4074.UTILITY ORD. #2938-96 |
| | 3) PLANS SHALL BE ROUTED TO THE PALM |
| | BEACH COUNTY HEALTH UNIT, 901 EVERNIA ST |
| | (561) 355-3018. PLANS SHALL BE STAMPED |
| | BY HEALTH DEPT PRIOR TO RESUBMITTING TO |
| | CITY W.P.B. 101.4.7 |
| | 4) SUBMIT CALCULATIONS FOR MINIMUM FAC- |
| | ILITIES PER TABLE 403.1. SHOW CALCS. FOR |
| | 15 NET. ALSO SECTION 403.1 POTTY PARITY |
| | SHALL BE ADHERED TO, 2 TO 3 RATIO. |
| | 5) SHT A-201 VOCATIOAN AREAS, WHAT IS |
| | THE USAGE OF THESE SPACES? SEC 104.2.1 |
| | 6) SUBMIT CALCULATIONS FOR PRIMARY AND |
| | SECONDARY ROOF DRAINS PER SECTIONS 1106 |
| | AND 1107 AND ALL SUBSECTIONS. WHEN SHOW- |
| | ING CALCULATIONS, SHOW 1/2 AREA OF ALL |
| | VERTICAL WALLS INCLUDING PARAPETS, AND |
| | THE AREA/AREAS OF ROOFS THAT DRAIN TO |
| | LOWER ROOFS FROM ABOVE. SECTIONS 1106.2 |
| | & 1106.4 |
| | 7) SHT A-202 WHERE 6 OR MORE STALLS ARE |
| | PROVIDED, IN ADDITION TO THE STALL COM- |
| | PLYING WITH 11-4.17.3, AT LEAST ONE |
| | STALL 36 IN. WIDE WITH AN OUTWARD SWING- |
| | ING, SELF CLOSING DOOR AND PARALLEL GRAB |
| | BARS COMPLYING WITH FIGURE 30(D) AND |
| | 11-4.26 SHALL BE PROVIDED. (WOMEN'S |
| | TOILET ROOM #223). |
| | 8) SHT A-403 SUBMIT DETAIL FOR SCUPPERS. |
| | SHOW HEIGHT AND WIDTH OF OPENING FOR ALL |
| | SCUPPERS. SEC 104.2.1 |
| | 9) SHT A-701 SUBMIT DETAIL FOR SHOWERS |
| | SHOWING SHOWER UNIT, (11-4.21.6), AND |
| | CURBS, (11-4.21.7). SEC 1104.2.1 |
| | 10) SHT A-702 DRESSING RM BENCHES SHALL |
| | COMPLY WITH 11-4.35.4. BENCHES SHALL BE |
| | FIXED TO WALL. SUBMIT DETAIL |
| | 11) A-703 FIXTURES & EQUIPMENT SCHEDULES |
| | DO NOT REFLECT THE FLOOR PLAN. ITEM F- |
| | 1004 NOT FOUND ON FLOOR PLAN. ITEM F- |
| | 1012 SAYS 3 COMPARTMENT SINK AND FLOOR |
| | PLAN SHOWS 2 COMPARTMENT SINK. PLEASE |
| | CLAIRFY. 104.2.1 |
| | 12) SHT P-5 DOMESTIC WATER ISOMETRIC, |
| | WATER HAMMER ARRESTOR SHALL BE LOCATED |
| | NEAR THE FIXTURE IN AN "EFFECTIVE RANGE" |
| | NOT IN THE CEILING AT THE TOP OF THE |
| | DROP. PDI-WH 201 & MANUF. INSTALLATION |
| | INSTRUCTIONS. |
| | 13) SHT P-5 DUPLEX STORM WATER PUMP, |
| | MANUF. INFORMATION REQUIRED. SEC 303.4 |
| | 14) SHT P-5 STORM DRAINAGE ISOMETRIC, |
| | INDICATE SLOPE OF PIPING FOR STORM. PIPE |
| | SHALL BE OF UNIFORM SLOPE. 3 AREAS OF |
| | RISER INDICATE THAT PIPE SIZING IS WRONG |
| | FOR 1/8" PER FOOT SLOPE. SEE HIGHLIGHTED |
| | AREAS. SEC 104.2.1 - TABLE 1106.3 |
| | 15) SHT P-6 INDICATE TOTAL NUMBER OF |
| | DRAINAGE FIXTURE UNITS FOR EACH SECTION |
| | OF RISER. 104.2.1 |
| | 16) SHT P-7 THERMAL EXPANSION CONTROL |
| | REQUIRED. SEC 607.3.2. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |