Plan Review Notes
Plan Review Notes For Permit 03061838
Permit Number 03061838
Review Stop P
Sequence Number 1
Notes
Date Text
2003-07-07 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FBC-2001 AMENDMENTS, CHAPTER
 1, ADMIN. CODE
  
 1) SHTS L-2.1 & L-2.2 SEPARATE IRRIGAT-
 ION PERMIT REQUIRED. RPZ BACKFLOW REQUI-
 RED IF POTABLE WATER USED FOR IRRIGATION
 SECTION 608.13.2
 2) GREASE INTECEPTOR SHALL BE SIZED BY
 RODNEY COMPO, ENVIRONMENTAL COMPLIANCE,
 INDUSTRIAL PRE-TREATMENT. PLEASE CONTACT
 @ (561) 837-4074.UTILITY ORD. #2938-96
 3) PLANS SHALL BE ROUTED TO THE PALM
 BEACH COUNTY HEALTH UNIT, 901 EVERNIA ST
 (561) 355-3018. PLANS SHALL BE STAMPED
 BY HEALTH DEPT PRIOR TO RESUBMITTING TO
 CITY W.P.B. 101.4.7
 4) SUBMIT CALCULATIONS FOR MINIMUM FAC-
 ILITIES PER TABLE 403.1. SHOW CALCS. FOR
 15 NET. ALSO SECTION 403.1 POTTY PARITY
 SHALL BE ADHERED TO, 2 TO 3 RATIO.
 5) SHT A-201 VOCATIOAN AREAS, WHAT IS
 THE USAGE OF THESE SPACES? SEC 104.2.1
 6) SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS PER SECTIONS 1106
 AND 1107 AND ALL SUBSECTIONS. WHEN SHOW-
 ING CALCULATIONS, SHOW 1/2 AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS, AND
 THE AREA/AREAS OF ROOFS THAT DRAIN TO
 LOWER ROOFS FROM ABOVE. SECTIONS 1106.2
 & 1106.4
 7) SHT A-202 WHERE 6 OR MORE STALLS ARE
 PROVIDED, IN ADDITION TO THE STALL COM-
 PLYING WITH 11-4.17.3, AT LEAST ONE
 STALL 36 IN. WIDE WITH AN OUTWARD SWING-
 ING, SELF CLOSING DOOR AND PARALLEL GRAB
 BARS COMPLYING WITH FIGURE 30(D) AND
 11-4.26 SHALL BE PROVIDED. (WOMEN'S
 TOILET ROOM #223).
 8) SHT A-403 SUBMIT DETAIL FOR SCUPPERS.
 SHOW HEIGHT AND WIDTH OF OPENING FOR ALL
 SCUPPERS. SEC 104.2.1
 9) SHT A-701 SUBMIT DETAIL FOR SHOWERS
 SHOWING SHOWER UNIT, (11-4.21.6), AND
 CURBS, (11-4.21.7). SEC 1104.2.1
 10) SHT A-702 DRESSING RM BENCHES SHALL
 COMPLY WITH 11-4.35.4. BENCHES SHALL BE
 FIXED TO WALL. SUBMIT DETAIL
 11) A-703 FIXTURES & EQUIPMENT SCHEDULES
 DO NOT REFLECT THE FLOOR PLAN. ITEM F-
 1004 NOT FOUND ON FLOOR PLAN. ITEM F-
 1012 SAYS 3 COMPARTMENT SINK AND FLOOR
 PLAN SHOWS 2 COMPARTMENT SINK. PLEASE
 CLAIRFY. 104.2.1
 12) SHT P-5 DOMESTIC WATER ISOMETRIC,
 WATER HAMMER ARRESTOR SHALL BE LOCATED
 NEAR THE FIXTURE IN AN "EFFECTIVE RANGE"
 NOT IN THE CEILING AT THE TOP OF THE
 DROP. PDI-WH 201 & MANUF. INSTALLATION
 INSTRUCTIONS.
 13) SHT P-5 DUPLEX STORM WATER PUMP,
 MANUF. INFORMATION REQUIRED. SEC 303.4
 14) SHT P-5 STORM DRAINAGE ISOMETRIC,
 INDICATE SLOPE OF PIPING FOR STORM. PIPE
 SHALL BE OF UNIFORM SLOPE. 3 AREAS OF
 RISER INDICATE THAT PIPE SIZING IS WRONG
 FOR 1/8" PER FOOT SLOPE. SEE HIGHLIGHTED
 AREAS. SEC 104.2.1 - TABLE 1106.3
 15) SHT P-6 INDICATE TOTAL NUMBER OF
 DRAINAGE FIXTURE UNITS FOR EACH SECTION
 OF RISER. 104.2.1
 16) SHT P-7 THERMAL EXPANSION CONTROL
 REQUIRED. SEC 607.3.2.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692