| Plan Review Notes For Permit 03061838 |
| Permit Number |
03061838 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2003-07-09 00:00:00 | DENIED: | | | | | | 1.PLAN SHEET M-1 CARBON MONOXIDE | | | DETECTORS, PLEASE PROVIDE MANUFACTURER | | | SUBMITTAL DATA AND INSTALLATION | | | INSTRUCTIONS. | | | | | | 2.LOCATION OF EXHAUST AND AIR MAKE-UP, | | | PLEASE CLARIFY THE ARRANGEMENT WILL | | | IT HAVE PROPER CROSS-VENTILATION? | | | | | | 3.M-1 PLEASE CLARIFY DETAIL, SHOULD | | | IT READ EXHAUST FAN 1 INSTEAD OF SUPPLY | | | FAN 1? | | | | | | 4.STAGE STORAGE #202 & ELECTRICAL RM | | | #207 - DUCT PENETRATING THROUGH RATED | | | WALLS SHALL COMPLY WITH 2001 FBC(M) | | | 607.1.3 EXCEPTIONS 1 - 4. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|